Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 16, 2015, 11:56 AM
Date
12/16/2015
W/O
0541712
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00717
PipeID
P14835
Time
3:56 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7018
Sewer Name
18 WORSHAM CREEK RELIEF TRUNK
City
WHITTIER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
11
Purpose
Capital Improvement Program Assesment
Project
20151216MDM_WORSHAM_CREEK_RELIEF_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Upstream MH
18 0983
Downstream MH
18 0984
Dir. of Survey
Upstream
Length Surveyed
161.5 ft.
Total Length
161.5 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
4
Overall Quick
Overall Rating
4
Pipe schematic from manhole 18 0983 to 18 0984
MH: 18 0983MH: 18 0984upstream0 ft. MSA - Survey Abandoned-COMPLETED BY REVERSE INSPECTION - INSPECTION COMPLETED REVERSE INSPECTION-SAG & DEBRIE STOPPED CAMERA0.2 ft. MCU - Camera Underwater, Finish - CAMERA STILL UNDER WATER9.2 ft. MCU - Camera Underwater, Start10.7 ft. MGO - General Observation - SAG IN LINE153.5 ft. MGP - General Photograph - 10" VCP161.5 ft. MWM - Water Mark, 30 %of cross sectional area161.5 ft. AMH - Downstream Manhole, Survey Begins - 3:55AM161.5 ft. MWL - Water Level, 10 %of cross sectional area161.5 ft. MGO - General Observation - MH CONN ACTIVE 9:00

Observation photos (2)

  • General Photograph - 10" VCP

    8 ft. - General Photograph - 10" VCP

  • General Observation - SAG IN LINE

    150.8 ft. - General Observation - SAG IN LINE

Observations (9)

DistanceCodeObservation
161.5MSAINSPECTION COMPLETED REVERSE INSPECTION-SAG & DEBRIE STOPPED CAMERA
0MWM
161.3MCUCAMERA STILL UNDER WATER
0AMH3:55AM
0MWL
0MGOMH CONN ACTIVE 9:00
150.8MGOSAG IN LINE
152.3MCU
8MGP10" VCP

Properties (6)

custom_field_three
SAG IN LINE
custom_field_two
3
customer
LACSD
datetime
2015-12-16T03:56:34-08:00
documentation
MARTIN,MANANES,OLIVER 111
is_lateral_inspection
false