- Date
- 12/15/2015
- W/O
- 0538789
- Weather
- Dry
- Operator/Surveyor
- MARTIN
- Sewer ID
- Z00784
- PipeID
- P16095
- Time
- 1:42 AM
- Certificate
- U-1014-06022543
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- H0003
- Sewer Name
- 21 SAN ANTONIO TRUNK
- City
- CLAREMONT
- Loc. details
- Main Highway - Urban
- Location Code
- A
- Use of Sewer
- Sanitary Sewer
- District
- District 21
- Page No.
- 06
- Purpose
- Capital Improvement Program Assesment
- Project
- 20151215MDM_SAN_ANTONIO_TRUNK
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 15 in.
- Upstream MH
- 21 0995
- Downstream MH
- 21 0994
- Dir. of Survey
- Downstream
- Length Surveyed
- 333.5 ft.
- Total Length
- 333.5 ft.
- Structural Index
- 2
- Structural Quick
- 5342
- Structural Rating
- 130
- O&M Index
- 0
- O&M Quick
- 0000
- O&M Rating
- 0
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 130
Pipe schematic from manhole 21 0995 to 21 0994 Observation photos (6)

54.1 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SLIGHT

69.8 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SLIGHT

127.2 ft. - General Photograph - 15" VCP

250.5 ft. - Broken Soil Visible, from 01 to 04 o'clock, within 8 inches of joint: YES

250.5 ft. - Broken Soil Visible, from 01 to 04 o'clock, within 8 inches of joint: YES

250.5 ft. - Broken Soil Visible, from 01 to 04 o'clock, within 8 inches of joint: YES