Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 2, 2015, 05:35 PM
  • Section#10_02 0169A_02 0169__SI_Date__SI_Preset.mp4

Date
12/02/2015
W/O
0536410
Weather
Dry
Operator/Surveyor
MIRANDA
Sewer ID
Z00251
PipeID
P02473
Time
9:35 AM
Certificate
U-1014-06022542
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7006
Sewer Name
02 DOWNEY-BELLFLOWER TRUNK
City
BELLFLOWER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
36
Purpose
Routine Assessment
Project
20151201AM_DOWNEY_BELLFLOWER_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Upstream MH
02 0169A
Downstream MH
02 0169
Dir. of Survey
Downstream
Length Surveyed
407.1 ft.
Total Length
407.1 ft.
Structural Index
3
Structural Quick
3221
Structural Rating
8
O&M Index
2
O&M Quick
2400
O&M Rating
8
Overall Index
2
Overall Quick
Overall Rating
16
Pipe schematic from manhole 02 0169A to 02 0169
MH: 02 0169AMH: 02 0169downstream0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MGO - General Observation - ACTIVE CONN. INSIDE THE MH. @ 03 O'CLOCK0 ft. MGO - General Observation - ROACHES INSIDE THE MH.0 ft. AMH - Upstream Manhole, Survey Begins - 9:37 AM0 ft. MWL - Water Level, 10 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Start35 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 4" - OPEN38.2 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6"40.1 ft. CM - Crack Multiple, from 07 to 04 o'clock, within 8 inches of joint: YES84.5 ft. TFD - Tap Factory Made Defective, at 01 o'clock, -, within 8 inches of joint: YES, 4" - ACTIVE87.8 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 6" - OPEN134.3 ft. TFD - Tap Factory Made Defective, at 01 o'clock, -, within 8 inches of joint: NO, 6" - OPEN, BROKEN137.7 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6"176.6 ft. TBA - Tap Break-In Active, at 01 o'clock, -, within 8 inches of joint: YES, 4"184.8 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES186.7 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6"189.6 ft. TFD - Tap Factory Made Defective, at 11 o'clock, -, within 8 inches of joint: YES, 6" - CAPPED, CRACKED235.9 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6"239 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6"283.8 ft. CM - Crack Multiple, from 11 to 02 o'clock, within 8 inches of joint: YES285.3 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6"288.5 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 4" - OPEN337 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6"340.1 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"385.4 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6"388.5 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6"404.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Finish405.8 ft. MGO - General Observation - ACTIVE CONN. INSIDE THE MH. @ 03 O'CLOCK405.8 ft. MGO - General Observation - ROACHES INSIDE THE MH.406.5 ft. MGO - General Observation - MOUSE INSIDE THE MH.407.1 ft. AMH - Downstream Manhole, Survey Ends - 10:08 AM

Observation photos (2)

  • Tap Factory Made Defective, at 01 o'clock, -, within 8 inches of joint: YES, 4" - ACTIVE

    84.5 ft. - Tap Factory Made Defective, at 01 o'clock, -, within 8 inches of joint: YES, 4" - ACTIVE

  • Tap Factory Made Defective, at 01 o'clock, -, within 8 inches of joint: NO, 6" - OPEN, BROKEN

    134.3 ft. - Tap Factory Made Defective, at 01 o'clock, -, within 8 inches of joint: NO, 6" - OPEN, BROKEN

Observations (31)

DistanceCodeObservation
0MWM
340.1TFA
404.8DAGS
0MGOACTIVE CONN. INSIDE THE MH. @ 03 O'CLOCK
283.8CM
134.3TFDOPEN, BROKEN
385.4TFC
35TFOPEN
235.9TFC
137.7TFC
40.1CM
186.7TFC
405.8MGOACTIVE CONN. INSIDE THE MH. @ 03 O'CLOCK
239TFC
0MGOROACHES INSIDE THE MH.
176.6TBA
184.8CL
87.8TFOPEN
405.8MGOROACHES INSIDE THE MH.
288.5TFOPEN
84.5TFDACTIVE
189.6TFDCAPPED, CRACKED
285.3TFC
407.1AMH10:08 AM
406.5MGOMOUSE INSIDE THE MH.
38.2TFC
2DAGS
0AMH9:37 AM
337TFC
0MWL
388.5TFC

Properties (5)

custom_field_two
4
customer
LACSD
datetime
2015-12-02T09:35:34-08:00
documentation
MIRANDA, FRANKLIN, SHADLER, MIRABAL
is_lateral_inspection
false