Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 16, 2019, 06:26 AM
  • 32 1169_32 1168 _08152019_234243.mp4

Date
08/15/2019
W/O
782269
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00839
PipeID
P19623
Time
11:26 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6864
Sewer Name
32 SAN FERNANDO ROAD TRUNK
City
SANTA CLARITA
Loc. details
Parking Lot
Location Code
G
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
09
Purpose
Routine Assessment
Project
RFIR_WO_782269_TV32021_AUG2019
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
32 1169
Downstream MH
32 1168
Dir. of Survey
Downstream
Length Surveyed
405.1 ft.
Total Length
405.1 ft.
Structural Index
3
Structural Quick
3O2O
Structural Rating
400
O&M Index
2
O&M Quick
312O
O&M Rating
163
Overall Index
2
Overall Quick
Overall Rating
563
Pipe schematic from manhole 32 1169 to 32 1168
MH: 32 1169MH: 32 1168downstream0 ft. AMH - Upstream Manhole, Survey Begins - 32 11690 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start58.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"96.8 ft. RMJ - Roots Medium Joint, from 03 to 09 o'clock, 15 %, within 8 inches of joint: YESR223.8 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"228.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"402.7 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish402.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish402.7 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish405.1 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK405.1 ft. AMH - Downstream Manhole, Survey Ends - 32 1168

Observation photos (4)

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Medium Joint, from 03 to 09 o'clock, 15 %, within 8 inches of joint: YESR

    96.8 ft. - Roots Medium Joint, from 03 to 09 o'clock, 15 %, within 8 inches of joint: YESR

Observations (15)

DistanceCodeObservation
2DAGS
402.7SAP
402.7DAGS
405.1MGOACTIVE CONNECTION AT MH 3 O'CLOCK
223.8TFA
96.8RMJ
2SAP
405.1AMH32 1168
2SSS
0AMH32 1169
0MWM
402.7SSS
228.5TFC
0MWL
58.3TFC

Properties (6)

additional_info
SC378334
custom_field_two
2
customer
LACSD
datetime
2019-08-15T23:26:28-07:00
documentation
PRO PIPE
is_lateral_inspection
false