Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 14, 2019, 09:02 AM
  • F 0153_F 0159 _01142019_013955.mpg

Date
01/14/2019
W/O
745610
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00043
PipeID
P10294
Time
1:02 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6323
Sewer Name
F JOINT OUTFALL F - UNIT 7A
City
NORWALK
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
37
Purpose
Routine Assessment
Project
RFIR_WO_745610_TV02202_JAN2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
51 in.
Width
51 in.
Upstream MH
F 0153
Downstream MH
F 0159
Dir. of Survey
Downstream
Length Surveyed
364.6 ft.
Total Length
364.6 ft.
Structural Index
4
Structural Quick
5G3M
Structural Rating
411
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
411
Pipe schematic from manhole F 0153 to F 0159
MH: F 0153MH: F 0159downstream0 ft. MGO - General Observation - CONNECTION AT MH 9 OCLOCK0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - F 01530 ft. MWL - Water Level, 20 %of cross sectional area2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start171.2 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start364.5 ft. MGO - General Observation - CONNECTION AT MH 3 OCLOCK364.5 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish364.5 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish364.6 ft. AMH - Downstream Manhole, Survey Ends - F 0159

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    171.2 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
364.5MGOCONNECTION AT MH 3 OCLOCK
364.5SRV
0MGOCONNECTION AT MH 9 OCLOCK
171.2SRV
2SAP
0MWM
0AMHF 0153
0MWL
364.5SAP
364.6AMHF 0159

Properties (6)

additional_info
SC365758
custom_field_two
2
customer
LACSD
datetime
2019-01-14T01:02:20-08:00
documentation
PROPIPE
is_lateral_inspection
false