Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 14, 2019, 09:40 AM
  • F 0159_F 0158 _01142019_015616.mpg

Date
01/14/2019
W/O
745610
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00043
PipeID
P10293
Time
1:40 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6323
Sewer Name
F JOINT OUTFALL F - UNIT 7A
City
NORWALK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
37
Purpose
Routine Assessment
Project
RFIR_WO_745610_TV02202_JAN2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
51 in.
Width
51 in.
Upstream MH
F 0159
Downstream MH
F 0158
Dir. of Survey
Downstream
Length Surveyed
464.1 ft.
Total Length
464.1 ft.
Structural Index
4
Structural Quick
5Q3Q
Structural Rating
736
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
736
Pipe schematic from manhole F 0159 to F 0158
MH: F 0159MH: F 0158downstream0 ft. AMH - Upstream Manhole, Survey Begins - F 01590 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 OCLOCK0 ft. MWM - Water Mark, 30 %of cross sectional area2.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.2 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start464.1 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish464.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish464.1 ft. AMH - Downstream Manhole, Survey Ends - F 0158

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2.2 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
464.1SRV
464.1SAP
0AMHF 0159
0MWL
0MGOCONNECTION AT MH 3 OCLOCK
464.1AMHF 0158
2.2SRV
2.1SAP
0MWM

Properties (6)

additional_info
SC365758
custom_field_two
2
customer
LACSD
datetime
2019-01-14T01:40:37-08:00
documentation
PROPIPE
is_lateral_inspection
false