Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 12, 2019, 09:34 AM
  • 02 0211_02 0210 _08122019_025536.mp4

Date
08/12/2019
W/O
782708
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00251
PipeID
P20566
Time
2:34 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6742
Sewer Name
02 DOWNEY-BELLFLOWER TRUNK
City
DOWNEY
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
30
Purpose
Routine Assessment
Project
RFIR_WO_782708_TV02382_AUG2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
02 0210
Downstream MH
02 0211
Dir. of Survey
Upstream
Length Surveyed
374 ft.
Total Length
374 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
5
Pipe schematic from manhole 02 0210 to 02 0211
MH: 02 0210MH: 02 0211upstream0 ft. AMH - Upstream Manhole, Survey Ends - 02 02110 ft. MGO - General Observation - CONNECTIONS AT BOTH 3 AND 9 O'CLOCK AT MH1.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish1.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish42.7 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"58.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"88.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"105.4 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"139.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"142.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"158.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"211.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"224.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"261.9 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: NO, 6"308.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"312.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"327 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"362 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"363.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start367.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start374 ft. MWL - Water Level, 20 %of cross sectional area374 ft. MWM - Water Mark, 35 %of cross sectional area374 ft. AMH - Downstream Manhole, Survey Begins - 02 0210

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    6.5 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    10.9 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (23)

DistanceCodeObservation
315.5TFC
61.8TFC
0MWL
372.1DAGS
47TF
331.3TFC
0MWM
162.5TF
231.5TFC
372.1CM
234.2TFC
285.2TF
374AMH02 0211
215.4TF
112.1TF
10.9CM
268.6TFA
12TFC
65.4TF
6.5DAGS
0AMH02 0210
374MGOCONNECTIONS AT BOTH 3 AND 9 O'CLOCK AT MH
149.5TF

Properties (6)

additional_info
SC378241
custom_field_two
3
customer
LACSD
datetime
2019-08-12T02:34:46-07:00
documentation
PROPIPE
is_lateral_inspection
false