Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 6, 2019, 06:34 AM
  • 02 0238_02 0237 _08052019_235254.mp4

Date
08/05/2019
W/O
782708
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00251
PipeID
P02546
Time
11:34 PM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6733
Sewer Name
02 DOWNEY-BELLFLOWER TRUNK
City
DOWNEY
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
28
Purpose
Routine Assessment
Project
RFIR_WO_782708_TV02382_AUG2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
02 0238
Downstream MH
02 0237
Dir. of Survey
Downstream
Length Surveyed
404.5 ft.
Total Length
404.5 ft.
Structural Index
4
Structural Quick
4O00
Structural Rating
320
O&M Index
2
O&M Quick
2O00
O&M Rating
160
Overall Index
3
Overall Quick
Overall Rating
480
Pipe schematic from manhole 02 0238 to 02 0237
MH: 02 0238MH: 02 0237downstream0 ft. MGO - General Observation - CONNECTIONS AT 3 AND 9 AT MH0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 02380 ft. MWM - Water Mark, 40 %of cross sectional area4.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start4.7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start137.3 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"140 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"235.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"238.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"334.7 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"337.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"402.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish402.5 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish404.5 ft. AMH - Downstream Manhole, Survey Ends - 02 0237

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    4.6 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.7 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (15)

DistanceCodeObservation
402.5DAGS
0MGOCONNECTIONS AT 3 AND 9 AT MH
137.3TFC
337.4TFC
235.5TFC
334.7TFC
4.6DAGS
140TFC
404.5AMH02 0237
4.7FM
0MWL
402.5FM
0AMH02 0238
0MWM
238.7TFC

Properties (6)

additional_info
SC378232
custom_field_two
3
customer
LACSD
datetime
2019-08-05T23:34:57-07:00
documentation
PROPIPE
is_lateral_inspection
false