Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 6, 2019, 06:57 AM
  • 02 0237_02 0236 _08062019_001212.mp4

Date
08/05/2019
W/O
782708
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00251
PipeID
P02545
Time
11:57 PM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6733
Sewer Name
02 DOWNEY-BELLFLOWER TRUNK
City
DOWNEY
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
27
Purpose
Routine Assessment
Project
RFIR_WO_782708_TV02382_AUG2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
02 0237
Downstream MH
02 0236
Dir. of Survey
Downstream
Length Surveyed
403.7 ft.
Total Length
403.7 ft.
Structural Index
4
Structural Quick
4O00
Structural Rating
316
O&M Index
2
O&M Quick
2O00
O&M Rating
158
Overall Index
3
Overall Quick
Overall Rating
474
Pipe schematic from manhole 02 0237 to 02 0236
MH: 02 0237MH: 02 0236downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 02370 ft. MWL - Water Level, 30 %of cross sectional area0 ft. MWM - Water Mark, 45 %of cross sectional area6 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start27.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"30 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"121.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"124 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"211.1 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"213.5 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"320.6 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"323.2 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"401.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish401.4 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish403.7 ft. AMH - Downstream Manhole, Survey Ends - 02 0236

Observation photos (2)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    6 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

Observations (16)

DistanceCodeObservation
403.7AMH02 0236
6FM
401.4DAGS
320.6TFC
211.1TFC
6DAGS
0AMH02 0237
323.2TFC
0MWL
401.4FM
121.2TFC
30TFC
213.5TFC
27.5TFC
124TFC
0MWM

Properties (6)

additional_info
SC378232
custom_field_two
3
customer
LACSD
datetime
2019-08-05T23:57:05-07:00
documentation
PROPIPE
is_lateral_inspection
false