Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 6, 2019, 11:01 AM
  • 02 0220_02 0219 _08062019_041313.mp4

Date
08/06/2019
W/O
782708
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00251
PipeID
P02526
Time
4:01 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6733
Sewer Name
02 DOWNEY-BELLFLOWER TRUNK
City
DOWNEY
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
27
Purpose
Routine Assessment
Project
RFIR_WO_782708_TV02382_AUG2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
02 0220
Downstream MH
02 0219
Dir. of Survey
Downstream
Length Surveyed
371.3 ft.
Total Length
371.3 ft.
Structural Index
4
Structural Quick
4M00
Structural Rating
284
O&M Index
2
O&M Quick
412N
O&M Rating
150
Overall Index
3
Overall Quick
Overall Rating
434
Pipe schematic from manhole 02 0220 to 02 0219
MH: 02 0220MH: 02 0219downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 02200 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MGO - General Observation - ABANDONED MH3.8 ft. DAGS - Deposits Attached Grease, 0 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start14.7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SPORADICALLY THROUGHOUT16.1 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"19.1 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"86.8 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: NO, 6"90.1 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"93.5 ft. TB - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: NO, 6"206.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"209 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"304.9 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"369.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish369.1 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish371.3 ft. AMH - Downstream Manhole, Survey Ends - 02 0219

Observation photos (3)

  • General Observation - ABANDONED MH

    0 ft. - General Observation - ABANDONED MH

  • Deposits Attached Grease, 0 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    3.8 ft. - Deposits Attached Grease, 0 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SPORADICALLY THROUGHOUT

    14.7 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SPORADICALLY THROUGHOUT

Observations (17)

DistanceCodeObservation
90.1TFC
369.1DAGS
86.8TF
206.2TF
369.1FM
3.8DAGS
0AMH02 0220
19.1TFC
0MWM
16.1TFC
209TFC
93.5TB
0MWL
14.7FMSPORADICALLY THROUGHOUT
371.3AMH02 0219
0MGOABANDONED MH
304.9TFA

Properties (6)

additional_info
SC378232
custom_field_two
3
customer
LACSD
datetime
2019-08-06T04:01:08-07:00
documentation
PROPIPE
is_lateral_inspection
false