Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 12, 2019, 08:41 AM
  • 02 0205_02 0204 _08122019_020104.mp4

Date
08/12/2019
W/O
782708
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00251
PipeID
P02514
Time
1:41 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6742
Sewer Name
02 DOWNEY-BELLFLOWER TRUNK
City
DOWNEY
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
30
Purpose
Routine Assessment
Project
RFIR_WO_782708_TV02382_AUG2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
02 0205
Downstream MH
02 0204
Dir. of Survey
Downstream
Length Surveyed
350.7 ft.
Total Length
350.7 ft.
Structural Index
3
Structural Quick
3M00
Structural Rating
207
O&M Index
2
O&M Quick
412Z
O&M Rating
278
Overall Index
2
Overall Quick
Overall Rating
485
Pipe schematic from manhole 02 0205 to 02 0204
MH: 02 0205MH: 02 0204downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 9 OCLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 02 02050 ft. MWL - Water Level, 35 %of cross sectional area4.5 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start4.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start8.9 ft. DSC - Deposits Settled Compacted, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start39.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"90 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"91.4 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: NO, 6"139.1 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"140.6 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"149.5 ft. MWL - Water Level, 45 %of cross sectional area176.1 ft. MGO - General Observation - LIGHT STEAM IN SEWER190.9 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"192.9 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"221.4 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"239 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"289.3 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"292.2 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"322.3 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 12"337.8 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"341 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"348.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish348.5 ft. DSC - Deposits Settled Compacted, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish348.5 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish350.6 ft. MGO - General Observation - CONNECTION AT MH 3 OCLOCK350.7 ft. AMH - Downstream Manhole, Survey Ends - 02 0204

Observation photos (2)

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    4.5 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    4.5 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

Observations (28)

DistanceCodeObservation
350.6MGOCONNECTION AT MH 3 OCLOCK
322.3TB
341TFC
140.6TFC
0MWM
176.1MGOLIGHT STEAM IN SEWER
4.5CM
221.4TFA
0MGOCONNECTION AT MH 9 OCLOCK
192.9TFC
337.8TFA
289.3TFC
348.5DAGS
149.5MWL
0AMH02 0205
91.4TF
292.2TFC
190.9TFC
348.5DSC
350.7AMH02 0204
39.5TFC
139.1TFC
4.5DAGS
90TFC
348.5CM
239TFC
0MWL
8.9DSC

Properties (6)

additional_info
SC378241
custom_field_two
3
customer
LACSD
datetime
2019-08-12T01:41:00-07:00
documentation
PROPIPE
is_lateral_inspection
false