Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 17, 2016, 11:23 AM
  • 16 0513_16 0512 _11172016_033234.mp4

Date
11/17/2016
W/O
596918
Weather
Dry
Operator/Surveyor
R.VARGAS
Sewer ID
Z00659
PipeID
P13564
Time
3:23 AM
Certificate
U-209-211
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3881
Sewer Name
16 LAMANDA PARK TRUNK
City
SAN MARINO
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
18
Purpose
Routine Assessment
Project
WO_596918_TV16026_NOV2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
27 in.
Width
27 in.
Upstream MH
16 0513
Downstream MH
16 0512
Dir. of Survey
Downstream
Length Surveyed
223.5 ft.
Total Length
223.5 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
1
O&M Quick
2114
O&M Rating
6
Overall Index
1
Overall Quick
Overall Rating
6
Pipe schematic from manhole 16 0513 to 16 0512
MH: 16 0513MH: 16 0512downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 16 05132.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start3.4 ft. TBA - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"3.4 ft. RFC - Roots Fine Connection, at 11 o'clock23.9 ft. TBA - Tap Break-In Active, at 01 o'clock, -, within 8 inches of joint: YES, 6"63.8 ft. TBA - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"83.5 ft. TBA - Tap Break-In Active, at 01 o'clock, -, within 8 inches of joint: YES, 6"124.8 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"124.8 ft. VC - Vermin Cockroach143.4 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"143.4 ft. RFL - Roots Fine Lateral, at 02 o'clock183.8 ft. TBA - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"221.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish223.4 ft. VC - Vermin Cockroach, within 8 inches of joint: NO - AT MH223.4 ft. MGO - General Observation - LATERAL AT MH 3 O CLOCK ACTIVE223.5 ft. AMH - Downstream Manhole, Survey Ends - 16 0512

Observation photos (8)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.4 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"

    3.4 ft. - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Break-In Active, at 01 o'clock, -, within 8 inches of joint: YES, 6"

    23.9 ft. - Tap Break-In Active, at 01 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"

    63.8 ft. - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Break-In Active, at 01 o'clock, -, within 8 inches of joint: YES, 6"

    83.5 ft. - Tap Break-In Active, at 01 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"

    124.8 ft. - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"

    143.4 ft. - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"

    183.8 ft. - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"

Observations (18)

DistanceCodeObservation
0MWL
221.7DAGS
3.4TBA
83.5TBA
63.8TBA
183.8TBA
223.4VCAT MH
143.4TBA
0MWM
223.5AMH16 0512
23.9TBA
124.8TBA
2.4DAGS
223.4MGOLATERAL AT MH 3 O CLOCK ACTIVE
3.4RFC
143.4RFL
124.8VC
0AMH16 0513

Properties (6)

additional_info
SC305213
custom_field_two
4
customer
LACSD
datetime
2016-11-17T03:23:08-08:00
documentation
PRO PIPE
is_lateral_inspection
false