Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 18, 2016, 11:30 AM
  • 16 0504_16 0503 _20161118_033020.mp4

Date
11/18/2016
W/O
596918
Weather
Dry
Operator/Surveyor
R.VARGAS
Sewer ID
Z00659
PipeID
P13555
Time
3:30 AM
Certificate
U-209-211
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3882
Sewer Name
16 LAMANDA PARK TRUNK
City
SAN MARINO
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
18
Purpose
Routine Assessment
Project
WO_596918_TV16026_NOV2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
30 in.
Width
30 in.
Upstream MH
16 0504
Downstream MH
16 0503
Dir. of Survey
Downstream
Length Surveyed
309.4 ft.
Total Length
309.4 ft.
Structural Index
1
Structural Quick
1100
Structural Rating
1
O&M Index
2
O&M Quick
3222
O&M Rating
12
Overall Index
2
Overall Quick
Overall Rating
13
Pipe schematic from manhole 16 0504 to 16 0503
MH: 16 0504MH: 16 0503downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 16 05040 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. VC - Vermin Cockroach0 ft. MGO - General Observation - LATERAL AT MH 3 O CLOCK ACTIVE2.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start16.9 ft. TBA - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"62.9 ft. TBA - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"112.3 ft. TBA - Tap Break-In Active, at 01 o'clock, -, within 8 inches of joint: YES, 6"120.6 ft. TBA - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"121.2 ft. CC - Crack Circumferential, from 10 to 11 o'clock, within 8 inches of joint: YES143 ft. TBA - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"170.5 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"183 ft. TBA - Tap Break-In Active, at 01 o'clock, -, within 8 inches of joint: YES, 6"200.2 ft. TBA - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"271 ft. RMC - Roots Medium Connection, from 09 to 01 o'clock, 30 %, within 8 inches of joint: YES271 ft. TBA - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"276 ft. RFL - Roots Fine Lateral, at 01 o'clock276 ft. TBA - Tap Break-In Active, at 01 o'clock, -, within 8 inches of joint: YES, 6"305 ft. RMC - Roots Medium Connection, from 11 to 01 o'clock, 15 %, within 8 inches of joint: YES305.7 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"308.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish309.4 ft. AMH - Downstream Manhole, Survey Ends - 16 0503

Observation photos (14)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.3 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"

    16.9 ft. - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"

    62.9 ft. - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Break-In Active, at 01 o'clock, -, within 8 inches of joint: YES, 6"

    112.3 ft. - Tap Break-In Active, at 01 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"

    120.6 ft. - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"

  • Crack Circumferential, from 10 to 11 o'clock, within 8 inches of joint: YES

    121.2 ft. - Crack Circumferential, from 10 to 11 o'clock, within 8 inches of joint: YES

  • Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"

    143 ft. - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"

    170.5 ft. - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Break-In Active, at 01 o'clock, -, within 8 inches of joint: YES, 6"

    183 ft. - Tap Break-In Active, at 01 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"

    200.2 ft. - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"

  • Roots Medium Connection, from 09 to 01 o'clock, 30 %, within 8 inches of joint: YES

    271 ft. - Roots Medium Connection, from 09 to 01 o'clock, 30 %, within 8 inches of joint: YES

  • Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"

    271 ft. - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Break-In Active, at 01 o'clock, -, within 8 inches of joint: YES, 6"

    276 ft. - Tap Break-In Active, at 01 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"

    305.7 ft. - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"

Observations (23)

DistanceCodeObservation
170.5TBA
62.9TBA
276RFL
271RMC
308.5DAGS
271TBA
16.9TBA
200.2TBA
121.2CC
0MWL
2.3DAGS
0AMH16 0504
305.7TBA
276TBA
143TBA
309.4AMH16 0503
305RMC
183TBA
112.3TBA
0MWM
120.6TBA
0VC
0MGOLATERAL AT MH 3 O CLOCK ACTIVE

Properties (6)

additional_info
SC305215
custom_field_two
4
customer
LACSD
datetime
2016-11-18T03:30:03-08:00
documentation
PRO PIPE
is_lateral_inspection
false