Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 17, 2016, 11:33 AM
  • 16 0512_16 0511 _11172016_034505.mp4

Date
11/17/2016
W/O
596918
Weather
Dry
Operator/Surveyor
R.VARGAS
Sewer ID
Z00659
PipeID
P13563
Time
3:33 AM
Certificate
U-209-211
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3881
Sewer Name
16 LAMANDA PARK TRUNK
City
SAN MARINO
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
18
Purpose
Routine Assessment
Project
WO_596918_TV16026_NOV2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
30 in.
Width
30 in.
Upstream MH
16 0512
Downstream MH
16 0511
Dir. of Survey
Downstream
Length Surveyed
54.5 ft.
Total Length
54.5 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2111
O&M Rating
3
Overall Index
2
Overall Quick
Overall Rating
3
Pipe schematic from manhole 16 0512 to 16 0511
MH: 16 0512MH: 16 0511downstream0 ft. AMH - Upstream Manhole, Survey Begins - 16 05120 ft. MGO - General Observation - LATERAL AT MH 3 O CLOCK ACTIVE0 ft. VC - Vermin Cockroach, within 8 inches of joint: NO - AT MH0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area2.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start18.9 ft. TBA - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"51.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish54.5 ft. AMH - Downstream Manhole, Survey Ends - 16 0511

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"

    18.9 ft. - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"

Observations (9)

DistanceCodeObservation
0AMH16 0512
0MGOLATERAL AT MH 3 O CLOCK ACTIVE
18.9TBA
54.5AMH16 0511
0VCAT MH
51.9DAGS
2.2DAGS
0MWM
0MWL

Properties (6)

additional_info
SC305213
custom_field_two
4
customer
LACSD
datetime
2016-11-17T03:33:23-08:00
documentation
PRO PIPE
is_lateral_inspection
false