Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 18, 2016, 12:13 PM
  • 16 0503_16 0502 _20161118_041334.mp4

Date
11/18/2016
W/O
596918
Weather
Dry
Operator/Surveyor
R.VARGAS
Sewer ID
Z00659
PipeID
P13554
Time
4:13 AM
Certificate
U-209-211
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3882
Sewer Name
16 LAMANDA PARK TRUNK
City
SAN MARINO
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
18
Purpose
Routine Assessment
Project
WO_596918_TV16026_NOV2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
30 in.
Width
30 in.
Upstream MH
16 0503
Downstream MH
16 0502
Dir. of Survey
Downstream
Length Surveyed
281.3 ft.
Total Length
281.3 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
312J
O&M Rating
114
Overall Index
2
Overall Quick
Overall Rating
114
Pipe schematic from manhole 16 0503 to 16 0502
MH: 16 0503MH: 16 0502downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 16 05032 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start7.7 ft. TBA - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"43.7 ft. TBA - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"62.6 ft. TBA - Tap Break-In Active, at 01 o'clock, -, within 8 inches of joint: YES, 6"128 ft. TBA - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"141 ft. RMC - Roots Medium Connection, from 12 to 02 o'clock, 20 %, within 8 inches of joint: YES141.9 ft. TBA - Tap Break-In Active, at 01 o'clock, -, within 8 inches of joint: YES, 6"153.4 ft. TBA - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"277.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish281.3 ft. VC - Vermin Cockroach281.3 ft. AMH - Downstream Manhole, Survey Ends - 16 0502281.3 ft. MGO - General Observation - LATERAL AT MH 3 O CLOCK ACTIVE

Observation photos (7)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"

    7.7 ft. - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"

    43.7 ft. - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Break-In Active, at 01 o'clock, -, within 8 inches of joint: YES, 6"

    62.6 ft. - Tap Break-In Active, at 01 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"

    128 ft. - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Break-In Active, at 01 o'clock, -, within 8 inches of joint: YES, 6"

    141.9 ft. - Tap Break-In Active, at 01 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"

    153.4 ft. - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"

Observations (15)

DistanceCodeObservation
0MWM
2DAGS
153.4TBA
281.3VC
141RMC
128TBA
62.6TBA
7.7TBA
277.4DAGS
281.3AMH16 0502
0MWL
141.9TBA
0AMH16 0503
281.3MGOLATERAL AT MH 3 O CLOCK ACTIVE
43.7TBA

Properties (6)

additional_info
SC305215
custom_field_two
4
customer
LACSD
datetime
2016-11-18T04:13:17-08:00
documentation
PRO PIPE
is_lateral_inspection