Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 17, 2016, 12:11 PM
  • 16 0509_16 0508 _11172016_043818.mp4

Date
11/17/2016
W/O
596918
Weather
Dry
Operator/Surveyor
R.VARGAS
Sewer ID
Z00659
PipeID
P13560
Time
4:11 AM
Certificate
U-209-211
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3881
Sewer Name
16 LAMANDA PARK TRUNK
City
SAN MARINO
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
18
Purpose
Routine Assessment
Project
WO_596918_TV16026_NOV2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
30 in.
Width
30 in.
Upstream MH
16 0509
Downstream MH
16 0508
Dir. of Survey
Downstream
Length Surveyed
259 ft.
Total Length
259 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
1
O&M Quick
2112
O&M Rating
4
Overall Index
1
Overall Quick
Overall Rating
4
Pipe schematic from manhole 16 0509 to 16 0508
MH: 16 0509MH: 16 0508downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 16 05093.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start7 ft. TB - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 6"34 ft. TBA - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"70.8 ft. TBA - Tap Break-In Active, at 01 o'clock, -, within 8 inches of joint: YES, 6"70.9 ft. RFL - Roots Fine Lateral, at 01 o'clock91.4 ft. TBA - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"150.7 ft. TBA - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"174.8 ft. VC - Vermin Cockroach207.6 ft. TBA - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"256.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish256.6 ft. TBA - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"259 ft. AMH - Downstream Manhole, Survey Ends - 16 0508259 ft. MGO - General Observation - LATERAL AT MH 3 O CLOCK ACTIVE

Observation photos (8)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    3.5 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 6"

    7 ft. - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"

    34 ft. - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Break-In Active, at 01 o'clock, -, within 8 inches of joint: YES, 6"

    70.8 ft. - Tap Break-In Active, at 01 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"

    91.4 ft. - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"

    150.7 ft. - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"

    207.6 ft. - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"

    256.6 ft. - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"

Observations (16)

DistanceCodeObservation
150.7TBA
256.6DAGS
259AMH16 0508
259MGOLATERAL AT MH 3 O CLOCK ACTIVE
207.6TBA
0MWM
91.4TBA
174.8VC
34TBA
0MWL
7TB
256.6TBA
3.5DAGS
70.8TBA
0AMH16 0509
70.9RFL

Properties (6)

additional_info
SC305213
custom_field_two
4
customer
LACSD
datetime
2016-11-17T04:11:28-08:00
documentation
PRO PIPE
is_lateral_inspection
false