Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 27, 2017, 07:39 PM
  • H 0402_H 0401A_10272017_131747.mp4

Date
10/27/2017
W/O
0663199
Weather
Dry
Operator/Surveyor
SANTIAGO OBREGON
Sewer ID
Z00177
PipeID
P22747
Time
12:39 PM
Certificate
U-1014-06022541
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7546
Sewer Name
H JOINT OUTFALL H - UNIT 5A
City
WHITTIER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
01
Purpose
Capital Improvement Program Assesment
Project
20171027SHO_JOINT_OUTFALL_H_UNIT_5A
Material
Reinforced Concrete Pipe
Shape
Circular
Height
60 in.
Upstream MH
H 0402
Downstream MH
H 0401A
Dir. of Survey
Downstream
Length Surveyed
24 ft.
Total Length
24 ft.
Structural Index
4
Structural Quick
5131
Structural Rating
8
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
8
Pipe schematic from manhole H 0402 to H 0401A
MH: H 0402MH: H 0401Adownstream0 ft. MWL - Water Level, 35 %of cross sectional area0 ft. MWM - Water Mark, 45 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01208 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO, Start8.3 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: NO, Start20.8 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO, Finish20.8 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: NO, Finish24 ft. AMH - Downstream Manhole, Survey Ends - 0125

Observation photos (2)

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO, Start

    8 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: NO, Start

    8.3 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: NO, Start

Observations (8)

DistanceCodeObservation
0MWL
20.8SRC
20.8SAP
8.3SAP
24AMH0125
0MWM
8SRC
0AMH0120

Properties (8)

additional_info
RFIR
custom_field_three
CORRODED REBAR & PROJECTING AGG.
custom_field_two
2
customer
LACSD
datetime
2017-10-27T12:39:51-07:00
documentation
OBREGON, IGNACIO, FRANKLIN, BRAR
is_lateral_inspection
false
year_laid
20000828