Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 26, 2016, 07:53 AM
  • 20 0263_20 0262_10262016_005358.mp4

Date
10/26/2016
W/O
597309
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00753
PipeID
P19230
Time
12:53 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3793
Sewer Name
20 35TH STREET EAST TRUNK
City
PALMDALE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 20
Page No.
13
Purpose
Routine Assessment
Project
WO_597309_TV20009_OCT2016
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
20 0263
Downstream MH
20 0262
Dir. of Survey
Downstream
Length Surveyed
37 ft.
Total Length
37 ft.
Structural Index
3
Structural Quick
3700
Structural Rating
21
O&M Index
2
O&M Quick
2700
O&M Rating
14
Overall Index
3
Overall Quick
Overall Rating
35
Pipe schematic from manhole 20 0263 to 20 0262
MH: 20 0263MH: 20 0262downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 20 02632 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start35.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish35.4 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish37 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK37 ft. AMH - Downstream Manhole, Survey Ends - 20 0262

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
37MGOACTIVE CONNECTION AT MH 3 O'CLOCK
2SAP
35.4DAGS
0MWL
37AMH20 0262
35.4SAP
0MWM
2DAGS
0AMH20 0263

Properties (6)

additional_info
SC306331
custom_field_two
3
customer
LACSD
datetime
2016-10-26T00:53:08-07:00
documentation
PRO PIPE
is_lateral_inspection
false