Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 5, 2016, 10:51 AM
  • 18 0107_18 0106 _05102016_040612.mp4

Date
10/05/2016
W/O
597011
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00698
PipeID
P13927
Time
3:51 AM
Certificate
U-507-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3730
Sewer Name
18 SANTA FE STREET TRUNK
City
WHITTIER, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
22
Purpose
Routine Assessment
Project
WO_597011_TV18083_OCT2016
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
18 0107
Downstream MH
18 0106
Dir. of Survey
Downstream
Length Surveyed
311.6 ft.
Total Length
311.7 ft.
Structural Index
3
Structural Quick
3K25
Structural Rating
193
O&M Index
2
O&M Quick
2K00
O&M Rating
122
Overall Index
2
Overall Quick
Overall Rating
315
Pipe schematic from manhole 18 0107 to 18 0106
MH: 18 0107MH: 18 0106downstream0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 01070.1 ft. MGO - General Observation - CONNECTION AT MH 3 ACTIVE2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start8.2 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"10.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"57.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"60.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"71.2 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES109.2 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"112.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"161.1 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"164.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"186.8 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES209.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"213.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4"258.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"261.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"263.4 ft. CL - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES308 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish308.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish308.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish311.7 ft. AMH - Downstream Manhole, Survey Ends - 18 0106

Observation photos (5)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.5 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.6 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    71.2 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    186.8 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

    263.4 ft. - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

Observations (26)

DistanceCodeObservation
308SAV
263.4CL
164.3TFC
261.6TFC
0.1MGOCONNECTION AT MH 3 ACTIVE
71.2CL
258.8TFA
112.1TFC
60.1TFC
311.7AMH18 0106
10.7TFC
186.8CL
8.2TFA
0MWM
109.2TFA
209.8TFA
308.9SSS
0MWL
213.2TF
2.5DAGS
0AMH18 0107
57.4TFC
161.1TFA
2SAV
2.6SSS
308.9DAGS

Properties (6)

additional_info
SC303717
custom_field_two
2
customer
LACSD
datetime
2016-10-05T03:51:00-07:00
documentation
PRO-PIPE
is_lateral_inspection
false