Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 6, 2016, 10:41 AM
  • 18 0076_18 0075A _06102016_035008.mp4

Date
10/06/2016
W/O
597011
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00698
PipeID
P13892
Time
3:41 AM
Certificate
U-507-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3731
Sewer Name
18 SANTA FE STREET TRUNK
City
WHITTIER, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
21
Purpose
Routine Assessment
Project
WO_597011_TV18083_OCT2016
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
18 0075A
Downstream MH
18 0076
Dir. of Survey
Upstream
Length Surveyed
141.5 ft.
Total Length
141.5 ft.
Structural Index
3
Structural Quick
3200
Structural Rating
6
O&M Index
2
O&M Quick
4127
O&M Rating
19
Overall Index
2
Overall Quick
Overall Rating
25
Pipe schematic from manhole 18 0075A to 18 0076
MH: 18 0075AMH: 18 0076upstream0 ft. AMH - Upstream Manhole, Survey Ends - 18 00760 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish2.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish21.3 ft. DAE - Deposits Attached Encrustation, 10 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES33 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES38.6 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, at 09 o'clock, , within 8 inches of joint: YES46.8 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES52.9 ft. IR - Infiltration Runner, at 04 o'clock, within 8 inches of joint: YES91.2 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, at 09 o'clock, , within 8 inches of joint: YES133.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start139.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start141.5 ft. MWL - Water Level, 5 %of cross sectional area141.5 ft. MWM - Water Mark, 20 %of cross sectional area141.5 ft. AMH - Downstream Manhole, Survey Begins - 18 0075A141.5 ft. VC - Vermin Cockroach

Observation photos (5)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    7.6 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Encrustation, 5 %of cross sectional area, at 09 o'clock,  , within 8 inches of joint: YES

    50.3 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, at 09 o'clock, , within 8 inches of joint: YES

  • Infiltration Runner, at 04 o'clock, within 8 inches of joint: YES

    88.6 ft. - Infiltration Runner, at 04 o'clock, within 8 inches of joint: YES

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 07 to 05 o'clock,  , within 8 inches of joint: YES

    94.7 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES

Observations (15)

DistanceCodeObservation
139SAV
141.5AMH18 0076
0MWL
94.7DAE
0MWM
108.5DAE
141.5DAGS
7.6DAGS
0AMH18 0075A
2SAV
102.9DAE
50.3DAE
120.2DAE
88.6IR
0VC

Properties (6)

additional_info
SC303718
custom_field_two
3
customer
LACSD
datetime
2016-10-06T03:41:00-07:00
documentation
PRO-PIPE
is_lateral_inspection
false