Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 6, 2016, 07:45 AM
  • 18 0100_18 0099 _06102016_005238.mp4

Date
10/06/2016
W/O
597011
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00698
PipeID
P13920
Time
12:45 AM
Certificate
U-507-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3731
Sewer Name
18 SANTA FE STREET TRUNK
City
WHITTIER, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
22
Purpose
Routine Assessment
Project
WO_597011_TV18083_OCT2016
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
18 0100
Downstream MH
18 0099
Dir. of Survey
Downstream
Length Surveyed
101.8 ft.
Total Length
101.8 ft.
Structural Index
3
Structural Quick
3C11
Structural Rating
61
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
61
Pipe schematic from manhole 18 0100 to 18 0099
MH: 18 0100MH: 18 0099downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 01000 ft. MWM - Water Mark, 20 %of cross sectional area2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start7.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"10.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"18.8 ft. CC - Crack Circumferential, from 07 to 10 o'clock, within 8 inches of joint: YES55.4 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"56.4 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"87.4 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"99.9 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish101.8 ft. AMH - Downstream Manhole, Survey Ends - 18 0099

Observation photos (2)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Circumferential, from 07 to 10 o'clock, within 8 inches of joint: YES

    18.8 ft. - Crack Circumferential, from 07 to 10 o'clock, within 8 inches of joint: YES

Observations (12)

DistanceCodeObservation
99.9SAV
2SAV
18.8CC
101.8AMH18 0099
55.4TFA
7.2TFC
10.1TF
0MWL
0AMH18 0100
56.4TFA
87.4TFA
0MWM

Properties (6)

additional_info
SC303718
custom_field_two
3
customer
LACSD
datetime
2016-10-06T00:45:00-07:00
documentation
PRO-PIPE
is_lateral_inspection
false