Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 5, 2016, 09:02 AM
  • 18 0113_18 0112 _05102016_021159.mp4

Date
10/05/2016
W/O
597011
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00698
PipeID
P13933
Time
2:02 AM
Certificate
U-507-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3730
Sewer Name
18 SANTA FE STREET TRUNK
City
WHITTIER, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
22
Purpose
Routine Assessment
Project
WO_597011_TV18083_OCT2016
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
18 0112
Downstream MH
18 0113
Dir. of Survey
Upstream
Length Surveyed
195.1 ft.
Total Length
195.1 ft.
Structural Index
3
Structural Quick
3G24
Structural Rating
122
O&M Index
2
O&M Quick
2F00
O&M Rating
74
Overall Index
2
Overall Quick
Overall Rating
196
Pipe schematic from manhole 18 0112 to 18 0113
MH: 18 0112MH: 18 0113upstream0 ft. AMH - Upstream Manhole, Survey Ends - 18 01130.6 ft. MGO - General Observation - CONNECTION AT MH 9 ACTIVE2.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Finish5.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish14 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES36.2 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES40.7 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4"49.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"92 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4"97.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"136.5 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES143.9 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: YES, 4"145.5 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES149.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"190.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Start193.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start195 ft. MWM - Water Mark, 15 %of cross sectional area195.1 ft. AMH - Downstream Manhole, Survey Begins - 18 0112195.1 ft. MWL - Water Level, 10 %of cross sectional area

Observation photos (5)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: NO, Start

    4.9 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    49.6 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    58.6 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    158.9 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    181.1 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

Observations (19)

DistanceCodeObservation
51.2TFA
97.6TFC
194.5MGOCONNECTION AT MH 9 ACTIVE
2SAV
58.6CL
45.8TFC
154.4TFA
0AMH18 0112
4.9DAGS
0.1MWM
0MWL
158.9CL
49.6CL
190SAV
145.6TFC
195.1AMH18 0113
192.4DAGS
103.1TFA
181.1CL

Properties (6)

additional_info
SC303717
custom_field_two
3
customer
LACSD
datetime
2016-10-05T02:02:00-07:00
documentation
PRO-PIPE
is_lateral_inspection
false