Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 7, 2016, 09:37 AM
  • 18 0078_18 1096 _07102016_024039.mp4

Date
10/07/2016
W/O
597011
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00698
PipeID
P13896
Time
2:37 AM
Certificate
U-507-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3732
Sewer Name
18 SANTA FE STREET TRUNK
City
WHITTIER, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
21
Purpose
Routine Assessment
Project
WO_597011_TV18083_OCT2016
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
18 1096
Downstream MH
18 0078
Dir. of Survey
Upstream
Length Surveyed
18.9 ft.
Total Length
18.9 ft.
Structural Index
2
Structural Quick
2200
Structural Rating
4
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
4
Pipe schematic from manhole 18 1096 to 18 0078
MH: 18 1096MH: 18 0078upstream0 ft. AMH - Upstream Manhole, Survey Ends - 18 00781.3 ft. SSS - Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish10.5 ft. SSS - Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES, Start - SEVERE18.9 ft. MWM - Water Mark, 10 %of cross sectional area18.9 ft. AMH - Downstream Manhole, Survey Begins - 18 109618.9 ft. MGO - General Observation - CONNECTION AT MH 3 ABANDONED18.9 ft. MWL - Water Level, 5 %of cross sectional area

Observation photos (1)

  • Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES, Start - SEVERE

    8.4 ft. - Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES, Start - SEVERE

Observations (7)

DistanceCodeObservation
0MWM
0AMH18 1096
8.4SSSSEVERE
0MGOCONNECTION AT MH 3 ABANDONED
18.9AMH18 0078
17.6SSS
0MWL

Properties (6)

additional_info
SC303719
custom_field_two
2
customer
LACSD
datetime
2016-10-07T02:37:00-07:00
documentation
PRO-PIPE
is_lateral_inspection
false