Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 7, 2016, 07:54 AM
  • 18 0064_18 0063 _07102016_010532.mp4

Date
10/07/2016
W/O
597011
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00698
PipeID
P13878
Time
12:54 AM
Certificate
U-507-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3732
Sewer Name
18 SANTA FE STREET TRUNK
City
WHITTIER, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
21
Purpose
Routine Assessment
Project
WO_597011_TV18083_OCT2016
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
18 0064
Downstream MH
18 0063
Dir. of Survey
Downstream
Length Surveyed
362 ft.
Total Length
362 ft.
Structural Index
3
Structural Quick
3200
Structural Rating
6
O&M Index
2
O&M Quick
2M11
O&M Rating
143
Overall Index
2
Overall Quick
Overall Rating
149
Pipe schematic from manhole 18 0064 to 18 0063
MH: 18 0064MH: 18 0063downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 00640 ft. MGO - General Observation - CONNECTION AT MH 3 ACTIVE2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start355 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish358.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish361.9 ft. MGO - General Observation - CONNECTION AT MH 3 ACTIVE362 ft. AMH - Downstream Manhole, Survey Ends - 18 0063362 ft. VC - Vermin Cockroach, within 8 inches of joint: NO

Observation photos (3)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    3.8 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Vermin Cockroach, within 8 inches of joint: NO

    362 ft. - Vermin Cockroach, within 8 inches of joint: NO

Observations (11)

DistanceCodeObservation
362AMH18 0063
361.9MGOCONNECTION AT MH 3 ACTIVE
3.8DAGS
358.1DAGS
362VC
2SAV
0MWL
355SAV
0MWM
0AMH18 0064
0MGOCONNECTION AT MH 3 ACTIVE

Properties (6)

additional_info
SC303719
custom_field_two
3
customer
LACSD
datetime
2016-10-07T00:54:00-07:00
documentation
PRO-PIPE
is_lateral_inspection
false