Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 7, 2016, 07:05 AM
  • 18 0067_18 0066 _07102016_001517.mp4

Date
10/07/2016
W/O
597011
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00698
PipeID
P13881
Time
12:05 AM
Certificate
U-507-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3732
Sewer Name
18 SANTA FE STREET TRUNK
City
WHITTIER, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
21
Purpose
Routine Assessment
Project
WO_597011_TV18083_OCT2016
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
18 0067
Downstream MH
18 0066
Dir. of Survey
Downstream
Length Surveyed
256.1 ft.
Total Length
256.1 ft.
Structural Index
3
Structural Quick
3I21
Structural Rating
152
O&M Index
2
O&M Quick
2211
O&M Rating
5
Overall Index
3
Overall Quick
Overall Rating
157
Pipe schematic from manhole 18 0067 to 18 0066
MH: 18 0067MH: 18 0066downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 00670 ft. VC - Vermin Cockroach0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start135.4 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES165 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 4"254 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish254.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish256.1 ft. AMH - Downstream Manhole, Survey Ends - 18 0066

Observation photos (2)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.7 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
2SAV
0AMH18 0067
0VC
0MWL
256.1AMH18 0066
165TBA
254SAV
135.4CL
254.3DAGS
2.7DAGS
0MWM

Properties (6)

additional_info
SC303719
custom_field_two
3
customer
LACSD
datetime
2016-10-07T00:05:00-07:00
documentation
PRO-PIPE
is_lateral_inspection
false