Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 7, 2016, 09:42 AM
  • 18 0079_18 0078 _07102016_025143.mp4

Date
10/07/2016
W/O
597011
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00698
PipeID
P13897
Time
2:42 AM
Certificate
U-507-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3732
Sewer Name
18 SANTA FE STREET TRUNK
City
WHITTIER, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
21
Purpose
Routine Assessment
Project
WO_597011_TV18083_OCT2016
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
18 0078
Downstream MH
18 0079
Dir. of Survey
Upstream
Length Surveyed
298.1 ft.
Total Length
298.2 ft.
Structural Index
3
Structural Quick
3222
Structural Rating
10
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
14
Pipe schematic from manhole 18 0078 to 18 0079
MH: 18 0078MH: 18 0079upstream0 ft. AMH - Upstream Manhole, Survey Ends - 18 00791 ft. SSS - Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish3.2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish11 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 4"269.6 ft. SSS - Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES, Start292.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start296.2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start298.2 ft. AMH - Downstream Manhole, Survey Begins - 18 0078298.2 ft. MWL - Water Level, 5 %of cross sectional area298.2 ft. MWM - Water Mark, 10 %of cross sectional area

Observation photos (3)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    6.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    28.6 ft. - Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
298.2AMH18 0079
297.2SSS
0AMH18 0078
287.2TFA
297.2DAGS
295SAV
6.1DAGS
0MWL
2SAV
28.6SSS
0MWM

Properties (6)

additional_info
SC303719
custom_field_two
2
customer
LACSD
datetime
2016-10-07T02:42:57-07:00
documentation
PRO-PIPE
is_lateral_inspection
false