Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 7, 2018, 09:28 AM
  • 04 0074_04 0038 _07022018_014549.mp4

Date
02/07/2018
W/O
685064
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00415
PipeID
P11811
Time
1:28 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5433
Sewer Name
04 SHERMAN TRUNK
City
WEST HOLLYWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 04
Page No.
03
Purpose
Routine Assessment
Project
WO_685064_TV04009_FEB2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
04 0074
Downstream MH
04 0038
Dir. of Survey
Downstream
Length Surveyed
248.9 ft.
Total Length
249 ft.
Structural Index
3
Structural Quick
3H21
Structural Rating
143
O&M Index
2
O&M Quick
4221
O&M Rating
13
Overall Index
3
Overall Quick
Overall Rating
156
Pipe schematic from manhole 04 0074 to 04 0038
MH: 04 0074MH: 04 0038downstream0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 04 00740 ft. MWL - Water Level, 5 %of cross sectional area9.9 ft. CL - Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES11.6 ft. IS - Infiltration Stain, from 08 to 04 o'clock, within 8 inches of joint: YES, Start11.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start26.1 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: NO, 6"29.1 ft. RFL - Roots Fine Lateral, at 02 o'clock29.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"74.9 ft. RBL - Roots Ball Lateral, at 02 o'clock, 95 % - INSIDE THE LATERAL74.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"77.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"77.3 ft. RFL - Roots Fine Lateral, at 10 o'clock77.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"126.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"128.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"136.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"178 ft. RBL - Roots Ball Lateral, at 10 o'clock, 55 %178 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"227.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"229 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"234.3 ft. DSZ - Deposits Settled Other, 5 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES241.1 ft. IS - Infiltration Stain, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish245.4 ft. RFJ - Roots Fine Joint, from 12 to 04 o'clock, within 8 inches of joint: YES246.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish249 ft. AMH - Downstream Manhole, Survey Ends - 04 0038

Observation photos (3)

  • Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES

    9.9 ft. - Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES

  • Infiltration Stain, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    11.6 ft. - Infiltration Stain, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    11.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (26)

DistanceCodeObservation
0MWM
241.1IS
29.1RFL
29.1TF
77.3TF
9.9CL
126.9TF
11.6IS
229TF
0AMH04 0074
0MWL
26.1TF
77.3RFL
178RBL
227.5TF
74.9RBLINSIDE THE LATERAL
136.9TFC
234.3DSZ
245.4RFJ
249AMH04 0038
74.9TF
77.5TF
128.8TF
11.6CM
246.3CM
178TF

Properties (6)

additional_info
SC347071
custom_field_two
3
customer
LACSD
datetime
2018-02-07T01:28:18-08:00
documentation
PROPIPE
is_lateral_inspection
false