Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 7, 2018, 09:14 AM
  • 04 0075_04 0074 _07022018_012742.mp4

Date
02/07/2018
W/O
685064
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00415
PipeID
P11812
Time
1:14 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5433
Sewer Name
04 SHERMAN TRUNK
City
WEST HOLLYWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 04
Page No.
01
Purpose
Routine Assessment
Project
WO_685064_TV04009_FEB2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
04 0075
Downstream MH
04 0074
Dir. of Survey
Downstream
Length Surveyed
253.4 ft.
Total Length
253.4 ft.
Structural Index
3
Structural Quick
3I00
Structural Rating
150
O&M Index
3
O&M Quick
4312
O&M Rating
14
Overall Index
3
Overall Quick
Overall Rating
164
Pipe schematic from manhole 04 0075 to 04 0074
MH: 04 0075MH: 04 0074downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 04 00750 ft. MWM - Water Mark, 15 %of cross sectional area4.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start4.3 ft. IS - Infiltration Stain, from 08 to 04 o'clock, within 8 inches of joint: YES, Start22.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"29.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"40.1 ft. TS - Tap Saddle, at 02 o'clock, -, within 8 inches of joint: NO, 6"76 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: NO, 6"78.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"124.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"127.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"127.3 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"127.3 ft. RBL - Roots Ball Lateral, at 10 o'clock, 80 %181.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"184.3 ft. RBL - Roots Ball Lateral, at 10 o'clock, 65 %184.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"228.1 ft. RFL - Roots Fine Lateral, at 02 o'clock228.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"230.1 ft. RFC - Roots Fine Connection, at 10 o'clock230.1 ft. RBL - Roots Ball Lateral, at 10 o'clock, 75 %230.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"253.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish253.4 ft. AMH - Downstream Manhole, Survey Ends - 04 0074253.4 ft. IS - Infiltration Stain, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (2)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Infiltration Stain, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.3 ft. - Infiltration Stain, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (25)

DistanceCodeObservation
4.3CM
253.4CM
0MWL
253.4AMH04 0074
253.4IS
4.3IS
29.7TFC
230.1RFC
127.3TF
181.8TF
76TF
228.1RFL
127.3TB
22.5TF
78.7TFC
184.3RBL
184.3TF
124.7TFC
230.1RBL
228.1TF
230.1TF
0AMH04 0075
127.3RBL
0MWM
40.1TS

Properties (6)

additional_info
SC347071
custom_field_two
3
customer
LACSD
datetime
2018-02-07T01:14:20-08:00
documentation
PROPIPE
is_lateral_inspection
false