Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 7, 2018, 09:01 AM
  • 04 0076_04 0075 _07022018_011350.mp4

Date
02/07/2018
W/O
685064
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00415
PipeID
P11813
Time
1:01 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5433
Sewer Name
04 SHERMAN TRUNK
City
WEST HOLLYWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 04
Page No.
01
Purpose
Routine Assessment
Project
WO_685064_TV04009_FEB2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
04 0076
Downstream MH
04 0075
Dir. of Survey
Downstream
Length Surveyed
256.5 ft.
Total Length
256.5 ft.
Structural Index
3
Structural Quick
3H21
Structural Rating
143
O&M Index
2
O&M Quick
2H00
O&M Rating
92
Overall Index
3
Overall Quick
Overall Rating
235
Pipe schematic from manhole 04 0076 to 04 0075
MH: 04 0076MH: 04 0075downstream0 ft. AMH - Upstream Manhole, Survey Begins - 04 00760 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 15 %of cross sectional area4.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES8.2 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES21.5 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start21.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start40 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"70.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"74.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"92.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"117.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"174.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"175.6 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: NO, 6"179 ft. MGO - General Observation - CHIPPING179.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"217.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"219.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"229.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"253.6 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish253.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish256.5 ft. AMH - Downstream Manhole, Survey Ends - 04 0075

Observation photos (4)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    4.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

    8.2 ft. - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start

    21.5 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    21.5 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (22)

DistanceCodeObservation
179.4TF
92.3TFC
219.3TF
21.5DAE
179MGOCHIPPING
256.5AMH04 0075
4.1CM
40TF
253.6DAE
0AMH04 0076
0MWL
217.5TF
8.2CL
21.5CM
117.2TF
70.5TF
174.1TF
0MWM
74.3TFC
175.6TF
253.6CM
229.5TFC

Properties (6)

additional_info
SC347071
custom_field_two
3
customer
LACSD
datetime
2018-02-07T01:01:44-08:00
documentation
PROPIPE
is_lateral_inspection
false