- Date
- 02/28/2018
- W/O
- 0692092
- Weather
- Dry
- Operator/Surveyor
- SANTIAGO OBREGON
- Sewer ID
- Z00340
- PipeID
- P10372
- Time
- 8:37 AM
- Certificate
- U-1014-06022541
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- G7640
- Sewer Name
- G JOINT OUTFALL G - UNIT 1(O)
- City
- COMPTON
- Loc. details
- Main Highway - Urban
- Location Code
- A
- Use of Sewer
- Sanitary Sewer
- District
- District 01
- Page No.
- 21
- Purpose
- Maintenance Related
- Project
- 20180228SHO_JOINT_OUTFALL_G_UNIT_1
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 54 in.
- Upstream MH
- G 0010
- Downstream MH
- G 0009
- Dir. of Survey
- Downstream
- Length Surveyed
- 156.8 ft.
- Total Length
- 156.8 ft.
- Structural Index
- 0
- Structural Quick
- 0000
- Structural Rating
- 0
- O&M Index
- 2
- O&M Quick
- 2100
- O&M Rating
- 2
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 2
Pipe schematic from manhole G 0010 to G 0009 Observation photos (2)

10.1 ft. - Deposits Settled Fine, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

156.8 ft. - Survey Abandoned - 15% DEBRIS IN THE LINE