- Date
- 02/23/2018
- W/O
- 0691943
- Weather
- Dry
- Operator/Surveyor
- MARTIN
- Sewer ID
- Z00312
- PipeID
- P02748
- Time
- 12:39 AM
- Certificate
- U-1014-06022543
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- HO751
- Sewer Name
- 02 70TH WAY EXTENSION TRUNK
- City
- PARAMOUNT
- Loc. details
- Main Highway - Urban
- Location Code
- A
- Use of Sewer
- Sanitary Sewer
- District
- District 02
- Page No.
- 35
- Purpose
- Routine Assessment
- Project
- 20180223MDM_70TH_WAY_EXTENSION_TRUNK
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 15 in.
- Upstream MH
- 02 0433
- Downstream MH
- 02 0425
- Dir. of Survey
- Upstream
- Length Surveyed
- 326.3 ft.
- Total Length
- 326.3 ft.
- Structural Index
- 2
- Structural Quick
- 4133
- Structural Rating
- 41
- O&M Index
- 2
- O&M Quick
- 4229
- O&M Rating
- 26
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 67
Pipe schematic from manhole 02 0433 to 02 0425 Observation photos (6)

10.2 ft. - Fracture Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES - MODERATE

10.3 ft. - General Observation - 15" VCP

201.2 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SL

242.2 ft. - General Observation - 25% MINERIAL DESPOSITE STOPPED CAMERA

242.2 ft. - Deposits Attached Encrustation, 25 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES

298.3 ft. - Deposits Attached Encrustation, 10 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES