Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 3, 2017, 12:47 PM
  • F 0076_F 0075A_03022017_044714.mpg

Date
02/03/2017
W/O
622202
Weather
Dry
Operator/Surveyor
R.VARGAS
Sewer ID
Z00037
PipeID
P10172
Time
4:47 AM
Certificate
U-209-211
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4105
Sewer Name
F JOINT OUTFALL F - UNIT 3B
City
CERRITOS
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
39
Purpose
V
Project
WO_622202_DISTRICT02_FEB2017
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
60 in.
Upstream MH
F 0076
Downstream MH
F 0075A
Dir. of Survey
Downstream
Length Surveyed
2.1 ft.
Total Length
2.1 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
4
Overall Quick
Overall Rating
7
Pipe schematic from manhole F 0076 to F 0075A
MH: F 0076MH: F 0075Adownstream0 ft. AMH - Upstream Manhole, Survey Begins - F 00760 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - Reversal Inspection2.1 ft. OBZ - Obstacles Other, 30 %of cross sectional area, from 04 to 08 o'clock - DEBRIS2.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES2.1 ft. MSA - Survey Abandoned - 30% DEBRIS2.1 ft. MGO - General Observation - MAGNESIUM H.O.

Observation photos (3)

  • Obstacles Other, 30 %of cross sectional area, from 04 to 08 o'clock - DEBRIS

    2.1 ft. - Obstacles Other, 30 %of cross sectional area, from 04 to 08 o'clock - DEBRIS

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES

    2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Survey Abandoned - 30% DEBRIS

    2.1 ft. - Survey Abandoned - 30% DEBRIS

Observations (8)

DistanceCodeObservation
0AMHF 0076
2.1OBZDEBRIS
2.1SAV
0MWM
2.1MSA30% DEBRIS
0MWL
0MGO
2.1MGOMAGNESIUM H.O.

Properties (6)

additional_info
SC318647
custom_field_two
5
customer
LACSD
datetime
2017-02-03T04:47:04-08:00
documentation
PRO PIPE
is_lateral_inspection
false