Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 22, 2017, 08:35 AM
  • 0_29 0192 _02222017_003531.mp4

Date
02/22/2017
W/O
619130
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z01025
PipeID
P24090
Time
12:35 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4248
Sewer Name
29 28TH STREET SEWER
City
SIGNAL HILL
Loc. details
Alley
Location Code
H
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
02
Purpose
Routine Assessment
Project
WO_619130_TV29101_FEB2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
29 0192
Downstream MH
0
Dir. of Survey
Upstream
Length Surveyed
134.7 ft.
Total Length
134.7 ft.
Structural Index
3
Structural Quick
5131
Structural Rating
9
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
9
Pipe schematic from manhole 29 0192 to 0
MH: 29 0192MH: 0upstream0 ft. AMH - Upstream Manhole, Survey Ends - 0, 6" CONNECTION NODE47.9 ft. JOM - Joint Offset Medium52.6 ft. H - Hole, from 10 to 03 o'clock, within 8 inches of joint: YES - WITH REPAIR VISIBLE86.6 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"89.4 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES90.4 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"114.3 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"124.6 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"127 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"134.7 ft. MWM - Water Mark, 5 %of cross sectional area134.7 ft. MWL - Water Level, 5 %of cross sectional area134.7 ft. AMH - Downstream Manhole, Survey Begins - 29 0192

Observation photos (3)

  • Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

    45.3 ft. - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Hole, from 10 to 03 o'clock, within 8 inches of joint: YES - WITH REPAIR VISIBLE

    82.1 ft. - Hole, from 10 to 03 o'clock, within 8 inches of joint: YES - WITH REPAIR VISIBLE

  • Joint Offset Medium

    86.8 ft. - Joint Offset Medium

Observations (12)

DistanceCodeObservation
20.4TFC
0MWM
48.1TFC
134.7AMH0, 6" CONNECTION NODE
45.3CM
82.1HWITH REPAIR VISIBLE
44.3TFC
0MWL
10.1TFA
0AMH29 0192
86.8JOM
7.7TFC

Properties (6)

additional_info
SC306951
custom_field_two
3
customer
LACSD
datetime
2017-02-22T00:35:15-08:00
documentation
PRO PIPE
is_lateral_inspection
false