Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 26, 2017, 11:16 AM
  • 20 0190_20 0189_01262017_031655.mp4

Date
01/26/2017
W/O
618960
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00739
PipeID
P19114
Time
3:16 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4221
Sewer Name
20 OUTFALL TRUNK
City
PALMDALE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 20
Page No.
08
Purpose
Routine Assessment
Project
WO_618960_TV20021_FEB2017
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
20 0189
Downstream MH
20 0190
Dir. of Survey
Upstream
Length Surveyed
349 ft.
Total Length
349 ft.
Structural Index
3
Structural Quick
3M00
Structural Rating
207
O&M Index
2
O&M Quick
2M00
O&M Rating
138
Overall Index
3
Overall Quick
Overall Rating
345
Pipe schematic from manhole 20 0189 to 20 0190
MH: 20 0189MH: 20 0190upstream0 ft. AMH - Upstream Manhole, Survey Ends - 20 01900 ft. MGO - General Observation - CAPPED CONNECTION AT MH 3 O'CLOCK0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK1.2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish1.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish47.7 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"51 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"96 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"99.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"145.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"148.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"197.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"200 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"248.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"251.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"297.9 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"300.8 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"346.9 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start346.9 ft. MGO - General Observation - MAG COATING 50%347 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start349 ft. MWL - Water Level, 10 %of cross sectional area349 ft. MWM - Water Mark, 30 %of cross sectional area349 ft. AMH - Downstream Manhole, Survey Begins - 20 0189

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (23)

DistanceCodeObservation
298TFC
349AMH20 0190
349MGOCAPPED CONNECTION AT MH 3 O'CLOCK
149TFC
100.6TFC
48.2TFC
347.8SAV
347.8DAGS
0MWL
349MGOACTIVE CONNECTION AT MH 9 O'CLOCK
0MWM
151.9TFC
2.1SAV
249.9TFC
200.6TFC
203.7TFC
0AMH20 0189
2DAGS
301.3TFC
253TFC
51.1TFC
97.4TFC
2.1MGOMAG COATING 50%

Properties (6)

additional_info
SC306723
custom_field_two
3
customer
LACSD
datetime
2017-01-26T03:16:26-08:00
documentation
PRO PIPE
is_lateral_inspection
false