Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 17, 2017, 06:17 AM
  • 05 1816_05 1815 _16022017_222034.mpg

Date
02/16/2017
W/O
618877
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00466
PipeID
P07039
Time
10:17 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4155
Sewer Name
05 JANET LANE TRUNK
City
TORRANCE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
31
Purpose
Routine Assessment
Project
WO_618877_TV05053_FEB2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
05 1816
Downstream MH
05 1815
Dir. of Survey
Downstream
Length Surveyed
186.7 ft.
Total Length
186.7 ft.
Structural Index
3
Structural Quick
5141
Structural Rating
41
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
41
Pipe schematic from manhole 05 1816 to 05 1815
MH: 05 1816MH: 05 1815downstream0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 18160 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK15.5 ft. CM - Crack Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES32.2 ft. B - Broken, from 02 to 04 o'clock, within 8 inches of joint: YES - JOINT BROKEN BUT HAS POSSIBLE REPAIR68.2 ft. CM - Crack Multiple, from 11 to 04 o'clock, within 8 inches of joint: YES71.6 ft. CM - Crack Multiple, from 07 to 04 o'clock, within 8 inches of joint: YES88.6 ft. CM - Crack Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES118.3 ft. CC - Crack Circumferential, from 02 to 05 o'clock, within 8 inches of joint: YES121.5 ft. CM - Crack Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES131.5 ft. CC - Crack Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES138.3 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES142.1 ft. CM - Crack Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES144.8 ft. CC - Crack Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES169.3 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 6"170.8 ft. FM - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES174.8 ft. CM - Crack Multiple, from 07 to 04 o'clock, within 8 inches of joint: YES178 ft. CM - Crack Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES181.8 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES186.7 ft. AMH - Downstream Manhole, Survey Ends - 05 1815

Observation photos (16)

  • Water Mark, 20 %of cross sectional area

    0 ft. - Water Mark, 20 %of cross sectional area

  • Crack Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES

    15.5 ft. - Crack Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES

  • Broken, from 02 to 04 o'clock, within 8 inches of joint: YES - JOINT BROKEN BUT HAS POSSIBLE REPAIR

    32.2 ft. - Broken, from 02 to 04 o'clock, within 8 inches of joint: YES - JOINT BROKEN BUT HAS POSSIBLE REPAIR

  • Crack Multiple, from 11 to 04 o'clock, within 8 inches of joint: YES

    68.2 ft. - Crack Multiple, from 11 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 07 to 04 o'clock, within 8 inches of joint: YES

    71.6 ft. - Crack Multiple, from 07 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES

    88.6 ft. - Crack Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES

  • Crack Circumferential, from 02 to 05 o'clock, within 8 inches of joint: YES

    118.3 ft. - Crack Circumferential, from 02 to 05 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES

    121.5 ft. - Crack Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES

  • Crack Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES

    131.5 ft. - Crack Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    138.3 ft. - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES

    142.1 ft. - Crack Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES

  • Crack Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES

    144.8 ft. - Crack Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

    170.8 ft. - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 07 to 04 o'clock, within 8 inches of joint: YES

    174.8 ft. - Crack Multiple, from 07 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES

    178 ft. - Crack Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    181.8 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

Observations (22)

DistanceCodeObservation
174.8CM
178CM
138.3CL
68.2CM
0MGOCONNECTION AT MH 9 O'CLOCK
169.3TF
15.5CM
131.5CC
0MWM
0MWL
32.2BJOINT BROKEN BUT HAS POSSIBLE REPAIR
186.7AMH05 1815
142.1CM
121.5CM
144.8CC
88.6CM
71.6CM
118.3CC
0AMH05 1816
170.8FM
181.8CM
0MGOCONNECTION AT MH 3 O'CLOCK

Properties (6)

additional_info
SC306861
custom_field_two
3
customer
LACSD
datetime
2017-02-16T22:17:13-08:00
documentation
PROPIPE
is_lateral_inspection
false