Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 11, 2016, 07:27 AM
  • 02 1383_02 1382_11102016_004512.mp4

Date
10/11/2016
W/O
597385
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00245
PipeID
P03903
Time
12:27 AM
Certificate
U-109-7948
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3427
Sewer Name
02 DITMAN STREET BRANCH TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
07A
Purpose
Routine Assessment
Project
WO_597385_TV02045_OCT2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
02 1383
Downstream MH
02 1382
Dir. of Survey
Downstream
Length Surveyed
357.5 ft.
Total Length
357.6 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
1
O&M Quick
1100
O&M Rating
1
Overall Index
1
Overall Quick
Overall Rating
1
Pipe schematic from manhole 02 1383 to 02 1382
MH: 02 1383MH: 02 1382downstream0 ft. MGO - General Observation - CONNECTION AT MH 9 ACTIVE0 ft. MGO - General Observation - CONNECTION AT MH 3 ACTIVE0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. VC - Vermin Cockroach0 ft. AMH - Upstream Manhole, Survey Begins - 02 13830.1 ft. MWM - Water Mark, 25 %of cross sectional area89.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"95.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"176.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"181.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"187.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"215.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"235.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"251.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"269.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"287.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"328.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"357.6 ft. AOC - Drop Connection, Survey Ends - 02 1382357.6 ft. TF - Tap Factory Made, at 06 o'clock, -, within 8 inches of joint: NO, 8"

Observations (19)

DistanceCodeObservation
0MGOCONNECTION AT MH 9 ACTIVE
251.1TF
269.4TF
0MGOCONNECTION AT MH 3 ACTIVE
176.1TF
187.8TF
95.1TF
0.1MWM
89.3TF
0MWL
0VC
287.3TF
181.4TF
328.3TFC
235.2TF
0AMH02 1383
215.4TF
357.6AOC02 1382
357.6TF

Properties (8)

additional_info
SC303461
custom_field_two
4
customer
LACSD
datetime
2016-10-11T00:27:53-07:00
documentation
PRO PIPE
is_lateral_inspection
false
lining
PVCP-Folded/Reformed
year_laid
38394