Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 1, 2016, 12:11 PM
  • 05 0785_05 0784 _01122016_041151.mp4

Date
12/01/2016
W/O
597374
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00553
PipeID
P06013
Time
4:11 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3839
Sewer Name
05 MANCHESTER-VERMONT DIVERSION EXTENSION TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
08
Purpose
Routine Assessment
Project
WO_597374_TV05320_OCT2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
05 0785
Downstream MH
05 0784
Dir. of Survey
Downstream
Length Surveyed
308.2 ft.
Total Length
308.2 ft.
Structural Index
3
Structural Quick
3K00
Structural Rating
183
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
183
Pipe schematic from manhole 05 0785 to 05 0784
MH: 05 0785MH: 05 0784downstream0 ft. AMH - Upstream Manhole, Survey Begins - 05 07850 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area4.6 ft. CM - Crack Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES7.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start308.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish308.2 ft. AMH - Downstream Manhole, Survey Ends - 05 0784

Observation photos (2)

  • Crack Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES

    4.6 ft. - Crack Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    7.7 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (7)

DistanceCodeObservation
4.6CM
0AMH05 0785
0MWM
7.7CM
0MWL
308.2CM
308.2AMH05 0784

Properties (6)

additional_info
SC304589
custom_field_two
3
customer
LACSD
datetime
2016-12-01T04:11:21-08:00
documentation
PROPIPE
is_lateral_inspection
false