Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 30, 2018, 08:02 AM
  • C 0306_C 0305 _30042018_012429.mp4

Date
04/30/2018
W/O
696324
Weather
Dry
Operator/Surveyor
B FUGATE
Sewer ID
Z00134
PipeID
P09766
Time
1:02 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5545
Sewer Name
C JOINT OUTFALL C - UNIT 6E
City
CERRITOS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
04
Purpose
Routine Assessment
Project
WO_696324_TV19035_APR2018
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
C 0306
Downstream MH
C 0305
Dir. of Survey
Downstream
Length Surveyed
284.4 ft.
Total Length
284.4 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
3
O&M Quick
3221
O&M Rating
8
Overall Index
3
Overall Quick
Overall Rating
13
Pipe schematic from manhole C 0306 to C 0305
MH: C 0306MH: C 0305downstream0 ft. AMH - Upstream Manhole, Survey Begins - C 03060 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MGO - General Observation - SERVICE CONNECTION AT 3 O' CLOCK AT MH0 ft. MGO - General Observation - SERVICE CONNECTION AT 9 O'CLOCK AT MH0 ft. MWL - Water Level, 15 %of cross sectional area2.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 05 o'clock, , within 8 inches of joint: NO2.5 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start54.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"62.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"74.9 ft. DAE - Deposits Attached Encrustation, 15 %of cross sectional area, from 02 to 05 o'clock, , within 8 inches of joint: YES102.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"110.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"150.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"158.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"198.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"207.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"254.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"262 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"276.4 ft. DSZ - Deposits Settled Other, 15 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES281.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish281.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish284.4 ft. AMH - Downstream Manhole, Survey Ends - C 0305284.4 ft. MGO - General Observation - SERVICE CONNECTION AT 9 O'CLOCK AT MH

Observation photos (4)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 05 o'clock,  , within 8 inches of joint: NO

    2.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 05 o'clock, , within 8 inches of joint: NO

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.5 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.3 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Encrustation, 15 %of cross sectional area, from 02 to 05 o'clock,  , within 8 inches of joint: YES

    74.9 ft. - Deposits Attached Encrustation, 15 %of cross sectional area, from 02 to 05 o'clock, , within 8 inches of joint: YES

Observations (24)

DistanceCodeObservation
0AMHC 0306
207.2TFC
262TFC
0MWM
284.4AMHC 0305
102.7TFC
0MGOSERVICE CONNECTION AT 3 O' CLOCK AT MH
2.1DAGS
3.3SSS
150.3TFC
0MGOSERVICE CONNECTION AT 9 O'CLOCK AT MH
54.9TFC
284.4MGOSERVICE CONNECTION AT 9 O'CLOCK AT MH
276.4DSZ
281.9SSS
0MWL
158.9TFC
74.9DAE
254.1TFC
110.6TFC
281.9SAP
198.2TFC
2.5SAP
62.9TFC

Properties (6)

additional_info
SC359303
custom_field_two
3
customer
LACSD
datetime
2018-04-30T01:02:46-07:00
documentation
PROPIPE
is_lateral_inspection
false