Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 1, 2018, 10:13 AM
  • C 0386_C 0385_01052018_033341.mp4

Date
05/01/2018
W/O
696316
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00142
PipeID
P09850
Time
3:13 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5549
Sewer Name
C JOINT OUTFALL C - UNIT 8D
City
LAKEWOOD
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
04
Purpose
Routine Assessment
Project
WO_696316_TV19067_APR2018
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Width
27 in.
Upstream MH
C 0386
Downstream MH
C 0385
Dir. of Survey
Downstream
Length Surveyed
408.3 ft.
Total Length
408.3 ft.
Structural Index
4
Structural Quick
5231
Structural Rating
15
O&M Index
3
O&M Quick
4121
O&M Rating
6
Overall Index
4
Overall Quick
Overall Rating
21
Pipe schematic from manhole C 0386 to C 0385
MH: C 0386MH: C 0385downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - C 03862.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.2 ft. MGO - General Observation - MAG COAT6.5 ft. IW - Infiltration Weeper, from 07 to 09 o'clock, within 8 inches of joint: YES25 ft. IS - Infiltration Stain, from 07 to 05 o'clock, within 8 inches of joint: YES68 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"88.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"185.9 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"307.2 ft. SRV - Surface Reinforcement Visible, from 03 to 05 o'clock, within 8 inches of joint: NO339.7 ft. SRV - Surface Reinforcement Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start402.7 ft. IR - Infiltration Runner, at 09 o'clock, within 8 inches of joint: NO406.7 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish406.7 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish406.7 ft. SRV - Surface Reinforcement Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish408.2 ft. MGO - General Observation - SERVICE CONNECTION AT 9 O'CLOCK AT MH408.3 ft. AMH - Downstream Manhole, Survey Ends - C 0385

Observation photos (7)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Infiltration Weeper, from 07 to 09 o'clock, within 8 inches of joint: YES

    6.5 ft. - Infiltration Weeper, from 07 to 09 o'clock, within 8 inches of joint: YES

  • Infiltration Stain, from 07 to 05 o'clock, within 8 inches of joint: YES

    25 ft. - Infiltration Stain, from 07 to 05 o'clock, within 8 inches of joint: YES

  • Surface Reinforcement Visible, from 03 to 05 o'clock, within 8 inches of joint: NO

    307.2 ft. - Surface Reinforcement Visible, from 03 to 05 o'clock, within 8 inches of joint: NO

  • Surface Reinforcement Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    339.7 ft. - Surface Reinforcement Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

  • Infiltration Runner, at 09 o'clock, within 8 inches of joint: NO

    402.7 ft. - Infiltration Runner, at 09 o'clock, within 8 inches of joint: NO

Observations (19)

DistanceCodeObservation
0MWL
406.7SSS
406.7SAP
406.7SRV
0MWM
6.5IW
2.2SSS
185.9TFA
339.7SRV
408.2MGOSERVICE CONNECTION AT 9 O'CLOCK AT MH
402.7IR
307.2SRV
0AMHC 0386
88.6TF
408.3AMHC 0385
68TFA
2.2MGOMAG COAT
2.1SAP
25IS

Properties (7)

additional_info
SC359305
custom_field_two
1
customer
LACSD
datetime
2018-05-01T03:13:12-07:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
26643