Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 2, 2018, 05:02 AM
  • 01 1203_01 1202_01052018_230039.mp4

Date
05/01/2018
W/O
695748
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00226
PipeID
P02114
Time
10:02 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5550
Sewer Name
01 WILCOX AVENUE TRUNK, EXTENSION #1
City
CUDAHY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
08
Purpose
Routine Assessment
Project
WO_695748_TV01206_APR2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 1203
Downstream MH
01 1202
Dir. of Survey
Downstream
Length Surveyed
197.3 ft.
Total Length
197.3 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
2111
O&M Rating
3
Overall Index
2
Overall Quick
Overall Rating
6
Pipe schematic from manhole 01 1203 to 01 1202
MH: 01 1203MH: 01 1202downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 12030 ft. MGO - General Observation - SERVICE CONNECTION AT 3 O' CLOCK AT MH0.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start22.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"82 ft. TFI - Tap Factory Made Intruding, at 02 o'clock, -, -, within 8 inches of joint: NO, 6", 1"116.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"153.4 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Start158.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"189.4 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Finish194.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish197.3 ft. AMH - Downstream Manhole, Survey Ends - 01 1202197.3 ft. MGO - General Observation - SERVICE CONNECTION AT 3 O' CLOCK AT MH

Observation photos (3)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    0.8 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Factory Made Intruding, at 02 o'clock, -, -, within 8 inches of joint: NO, 6", 1"

    82 ft. - Tap Factory Made Intruding, at 02 o'clock, -, -, within 8 inches of joint: NO, 6", 1"

  • Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Start

    153.4 ft. - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Start

Observations (14)

DistanceCodeObservation
22.5TFC
189.4RFJ
197.3AMH01 1202
158.4TFC
0MWL
116.2TF
0MWM
194.4CM
82TFI
0AMH01 1203
153.4RFJ
0MGOSERVICE CONNECTION AT 3 O' CLOCK AT MH
197.3MGOSERVICE CONNECTION AT 3 O' CLOCK AT MH
0.8CM

Properties (6)

additional_info
SC359306
custom_field_two
3
customer
LACSD
datetime
2018-05-01T22:02:20-07:00
documentation
PROPIPE
is_lateral_inspection
false