Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 2, 2018, 09:06 AM
  • 01 1199_01 1198_02052018_021836.mp4

Date
05/02/2018
W/O
695748
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00226
PipeID
P02109
Time
2:06 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5550
Sewer Name
01 WILCOX AVENUE TRUNK, EXTENSION #1
City
CUDAHY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
11
Purpose
Routine Assessment
Project
WO_695748_TV01206_APR2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 1198
Downstream MH
01 1199
Dir. of Survey
Upstream
Length Surveyed
305.6 ft.
Total Length
305.6 ft.
Structural Index
3
Structural Quick
3222
Structural Rating
10
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
10
Pipe schematic from manhole 01 1198 to 01 1199
MH: 01 1198MH: 01 1199upstream0 ft. MGO - General Observation - SERVICE CONNECTION AT 9 O'CLOCK AT MH0 ft. AMH - Upstream Manhole, Survey Ends - 01 11990 ft. MGO - General Observation - SERVICE CONNECTION AT 3 O' CLOCK AT MH0.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish55.4 ft. SSS - Surface Spalling, at 12 o'clock, within 8 inches of joint: NO172.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start173 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish270.6 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start277 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish303.5 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start305.6 ft. MWL - Water Level, 15 %of cross sectional area305.6 ft. MWM - Water Mark, 40 %of cross sectional area305.6 ft. AMH - Downstream Manhole, Survey Begins - 01 1198305.6 ft. MGO - General Observation - SERVICE CONNECTION AT 2 O' CLOCK AT MH

Observation photos (4)

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    35 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    132.7 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, at 12 o'clock, within 8 inches of joint: NO

    250.2 ft. - Surface Spalling, at 12 o'clock, within 8 inches of joint: NO

Observations (14)

DistanceCodeObservation
2.1FL
0MWL
305.6MGOSERVICE CONNECTION AT 9 O'CLOCK AT MH
132.7CM
305.5CM
0MWM
305.6AMH01 1199
132.6CL
28.6FL
0AMH01 1198
250.2SSS
305.6MGOSERVICE CONNECTION AT 3 O' CLOCK AT MH
35CL
0MGOSERVICE CONNECTION AT 2 O' CLOCK AT MH

Properties (6)

additional_info
SC359306
custom_field_two
2
customer
LACSD
datetime
2018-05-02T02:06:24-07:00
documentation
PROPIPE
is_lateral_inspection
false