Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 4, 2018, 08:37 AM
  • 01 0017_01 0016_04052018_015030.mp4

Date
05/04/2018
W/O
695657
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00209
PipeID
P00682
Time
1:37 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5658
Sewer Name
01 HOOPER AVENUE-COMPTON CREEK TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
16
Purpose
Routine Assessment
Project
WO_695657_TV01245_APR2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
27 in.
Width
27 in.
Upstream MH
01 0017
Downstream MH
01 0016
Dir. of Survey
Downstream
Length Surveyed
428.5 ft.
Total Length
428.6 ft.
Structural Index
3
Structural Quick
3O00
Structural Rating
246
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
246
Pipe schematic from manhole 01 0017 to 01 0016
MH: 01 0017MH: 01 0016downstream0 ft. AMH - Upstream Manhole, Survey Begins - 01 00170 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK3.6 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start261.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"333.6 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"373.7 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish387.1 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start387.3 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"425.2 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish428.6 ft. AMH - Downstream Manhole, Survey Ends - 01 0016

Observation photos (2)

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    3.6 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    387.1 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
3.6CM
373.7CM
333.6TB
261.9TF
0AMH01 0017
428.6AMH01 0016
387.3TB
425.2CM
0MWM
0MWL
0MGOCONNECTION AT MH 9 O'CLOCK
387.1CM
0MGOCONNECTION AT MH 3 O'CLOCK

Properties (6)

additional_info
SC395313
custom_field_two
3
customer
LACSD
datetime
2018-05-04T01:37:17-07:00
documentation
PROPIPE
is_lateral_inspection
false