Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 4, 2019, 07:38 AM
  • 02 1156_02 1155_04042019_005412.mp4

Date
04/04/2019
W/O
761209
Weather
Dry
Operator/Surveyor
E.RUIZ
Sewer ID
Z00351
PipeID
P02940
Time
12:38 AM
Certificate
U-715-07000753
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6512
Sewer Name
02 GARFIELD AVENUE EXTENSION TRUNK
City
MONTEBELLO
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
09
Purpose
Routine Assessment
Project
RFIR_WO_761209_TV02318_APR2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
02 1156
Downstream MH
02 1155
Dir. of Survey
Downstream
Length Surveyed
286.2 ft.
Total Length
286.2 ft.
Structural Index
3
Structural Quick
4222
Structural Rating
12
O&M Index
2
O&M Quick
2J00
O&M Rating
114
Overall Index
2
Overall Quick
Overall Rating
126
Pipe schematic from manhole 02 1156 to 02 1155
MH: 02 1156MH: 02 1155downstream0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 11560 ft. MWL - Water Level, 15 %of cross sectional area1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start7.2 ft. CL - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES10.2 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES11.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"16.3 ft. FM - Fracture Multiple, from 01 to 05 o'clock, within 8 inches of joint: YES25.6 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start60.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"110.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"159.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"208.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"261 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"283.4 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish286 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish286.2 ft. AMH - Downstream Manhole, Survey Ends - 02 1155

Observation photos (4)

  • Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

    7.2 ft. - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    10.2 ft. - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 01 to 05 o'clock, within 8 inches of joint: YES

    16.3 ft. - Fracture Multiple, from 01 to 05 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    25.6 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (17)

DistanceCodeObservation
7.2CL
283.4FM
261TFC
1DAGS
208.5TFC
286DAGS
25.6FM
16.3FM
0MWM
159.1TFC
10.2CL
11.6TFC
0AMH02 1156
286.2AMH02 1155
110.1TFC
0MWL
60.8TFC

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2019-04-04T00:38:59-07:00
documentation
PROPIPE
is_lateral_inspection
false