Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 8, 2019, 11:14 AM
  • 02 1133_02 1132_04082019_042959.mp4

Date
04/08/2019
W/O
761209
Weather
Dry
Operator/Surveyor
E.RUIZ
Sewer ID
Z00351
PipeID
P02915
Time
4:14 AM
Certificate
U-715-07000753
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6515
Sewer Name
02 GARFIELD AVENUE EXTENSION TRUNK
City
MONTEBELLO
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
13
Purpose
Routine Assessment
Project
RFIR_WO_761209_TV02318_APR2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
02 1133
Downstream MH
02 1132
Dir. of Survey
Downstream
Length Surveyed
193.1 ft.
Total Length
193.1 ft.
Structural Index
4
Structural Quick
4F00
Structural Rating
148
O&M Index
2
O&M Quick
4131
O&M Rating
87
Overall Index
3
Overall Quick
Overall Rating
235
Pipe schematic from manhole 02 1133 to 02 1132
MH: 02 1133MH: 02 1132downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 11330 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MGO - General Observation - MULTIPLE CONNECTIONS IN MH0 ft. MWL - Water Level, 30 %of cross sectional area1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, at 09 o'clock, , within 8 inches of joint: YES, Start6 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start96.1 ft. RFJ - Roots Fine Joint, from 08 to 12 o'clock, within 8 inches of joint: YES104.1 ft. RFJ - Roots Fine Joint, from 08 to 02 o'clock, within 8 inches of joint: YES108.3 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES116.1 ft. RMJ - Roots Medium Joint, from 08 to 04 o'clock, 15 %, within 8 inches of joint: YESR, Start132.4 ft. RMJ - Roots Medium Joint, from 08 to 04 o'clock, 15 %, within 8 inches of joint: YESR, Finish132.7 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start189.7 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish189.7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish193 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, at 09 o'clock, , within 8 inches of joint: YES, Finish193.1 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK193.1 ft. AMH - Downstream Manhole, Survey Ends - 02 1132

Observation photos (7)

  • Deposits Attached Grease, 5 %of cross sectional area, at 09 o'clock,  , within 8 inches of joint: YES, Start

    1 ft. - Deposits Attached Grease, 5 %of cross sectional area, at 09 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Joint, from 08 to 12 o'clock, within 8 inches of joint: YES

    96.1 ft. - Roots Fine Joint, from 08 to 12 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 08 to 02 o'clock, within 8 inches of joint: YES

    104.1 ft. - Roots Fine Joint, from 08 to 02 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES

    108.3 ft. - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Roots Medium Joint, from 08 to 04 o'clock, 15 %, within 8 inches of joint: YESR, Start

    116.1 ft. - Roots Medium Joint, from 08 to 04 o'clock, 15 %, within 8 inches of joint: YESR, Start

  • Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    132.7 ft. - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (17)

DistanceCodeObservation
189.7RFJ
132.7RFJ
0AMH02 1133
0MWM
6FM
132.4RMJ
108.3RFJ
193.1MGOCONNECTION AT MH 3 O'CLOCK
189.7FM
0MGOMULTIPLE CONNECTIONS IN MH
193DAGS
193.1AMH02 1132
96.1RFJ
0MWL
1DAGS
104.1RFJ
116.1RMJ

Properties (5)

custom_field_two
2
customer
LACSD
datetime
2019-04-08T04:14:43-07:00
documentation
PROPIPE
is_lateral_inspection
false