Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 4, 2019, 09:30 AM
  • 02 1149_02 1148_04042019_023808.mp4

Date
04/04/2019
W/O
761209
Weather
Dry
Operator/Surveyor
E.RUIZ
Sewer ID
Z00351
PipeID
P02933
Time
2:30 AM
Certificate
U-715-07000753
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6512
Sewer Name
02 GARFIELD AVENUE EXTENSION TRUNK
City
MONTEBELLO
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
13
Purpose
Routine Assessment
Project
RFIR_WO_761209_TV02318_APR2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
02 1149
Downstream MH
02 1148
Dir. of Survey
Downstream
Length Surveyed
121.9 ft.
Total Length
121.9 ft.
Structural Index
4
Structural Quick
4D00
Structural Rating
92
O&M Index
3
O&M Quick
3D00
O&M Rating
72
Overall Index
3
Overall Quick
Overall Rating
164
Pipe schematic from manhole 02 1149 to 02 1148
MH: 02 1149MH: 02 1148downstream0 ft. DAGS - Deposits Attached Grease, 15 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start0 ft. MGO - General Observation - SERVICE CONNECTION AT 3 O' CLOCK AT MH0 ft. AMH - Upstream Manhole, Survey Begins - 02 11490 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area5.2 ft. FM - CrackMultiple, from 07 to 05 o'clock, within 8 inches of joint: YES, Start19.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"71.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"110.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"119.4 ft. FM - Crack Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish121 ft. DAGS - Deposits Attached Grease, 15 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish121.9 ft. AMH - Downstream Manhole, Survey Ends - 02 1148121.9 ft. MGO - General Observation - SERVICE CONNECTION AT 9 O'CLOCK AT MH

Observation photos (1)

  • CrackMultiple, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    5.2 ft. - CrackMultiple, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
110.5TFC
0DAGS
0MGOSERVICE CONNECTION AT 3 O' CLOCK AT MH
121DAGS
0AMH02 1149
5.2FM
19.1TFC
121.9AMH02 1148
71.2TFC
0MWM
119.4FM
0MWL
121.9MGOSERVICE CONNECTION AT 9 O'CLOCK AT MH

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2019-04-04T02:30:25-07:00
documentation
PROPIPE
is_lateral_inspection
false