Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 30, 2019, 09:23 AM
  • 02 1121_02 1120 _04302019_023510.mp4

Date
04/30/2019
W/O
761209
Weather
Dry
Operator/Surveyor
E.RUIZ
Sewer ID
Z00351
PipeID
P02900
Time
2:23 AM
Certificate
U-715-07000753
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6524
Sewer Name
02 GARFIELD AVENUE EXTENSION TRUNK
City
MONTEBELLO
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
14
Purpose
Routine Assessment
Project
RFIR_WO_761209_TV02318_APR2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
02 1121
Downstream MH
02 1120
Dir. of Survey
Downstream
Length Surveyed
292.1 ft.
Total Length
292.1 ft.
Structural Index
4
Structural Quick
4100
Structural Rating
4
O&M Index
2
O&M Quick
2K00
O&M Rating
116
Overall Index
2
Overall Quick
Overall Rating
120
Pipe schematic from manhole 02 1121 to 02 1120
MH: 02 1121MH: 02 1120downstream0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. MWM - Water Mark, 45 %of cross sectional area0 ft. AMH - Downstream Manhole, Survey Begins - 02 11200 ft. MGO - General Observation - CONNECTION IN MH 9 OCLOCK1 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start7.6 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start10.9 ft. MGO - General Observation - MAG COAT THROUGHOUT158.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"202.3 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 8"205.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"256.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"259.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"288.7 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish292 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish292.1 ft. AMH - Downstream Manhole, Survey Ends - 02 1120

Observation photos (1)

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    7.6 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (15)

DistanceCodeObservation
1DAGS
158.1TFC
0MWL
256.8TFC
202.3TFA
288.7FM
292DAGS
0MWM
0AMH02 1120
205.5TFC
0MGOCONNECTION IN MH 9 OCLOCK
292.1AMH02 1120
259.5TFC
7.6FM
10.9MGOMAG COAT THROUGHOUT

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2019-04-30T02:23:36-07:00
documentation
PROPIPE
is_lateral_inspection
false