Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 5, 2019, 10:25 AM
  • 02 1144_02 1143_04052019_033434.mp4

Date
04/05/2019
W/O
761209
Weather
Dry
Operator/Surveyor
E.RUIZ
Sewer ID
Z00351
PipeID
P02928
Time
3:25 AM
Certificate
U-715-07000753
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6514
Sewer Name
02 GARFIELD AVENUE EXTENSION TRUNK
City
MONTEBELLO
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
13
Purpose
Routine Assessment
Project
RFIR_WO_761209_TV02318_APR2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
02 1143
Downstream MH
02 1144
Dir. of Survey
Upstream
Length Surveyed
231.2 ft.
Total Length
231.2 ft.
Structural Index
4
Structural Quick
4100
Structural Rating
4
O&M Index
2
O&M Quick
2H00
O&M Rating
92
Overall Index
2
Overall Quick
Overall Rating
96
Pipe schematic from manhole 02 1143 to 02 1144
MH: 02 1143MH: 02 1144upstream0 ft. AMH - Upstream Manhole, Survey Ends - 02 11440 ft. MGO - General Observation - SERVICE CONNECTION AT 9 O'CLOCK AT MH0.2 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish2.5 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish27.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"81.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"133.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"226.5 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start230.7 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start231.2 ft. MWM - Water Mark, 30 %of cross sectional area231.2 ft. MGO - General Observation - SERVICE CONNECTION AT 3 O' CLOCK AT MH231.2 ft. MWL - Water Level, 15 %of cross sectional area231.2 ft. MGO - General Observation - CAPPED CONNECTION AT 9 O' CLOCK AT231.2 ft. AMH - Downstream Manhole, Survey Begins - 02 1143

Observation photos (1)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.7 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
0.5DAGS
0MWM
231.2AMH02 1144
204TFC
149.8TFC
228.7FM
0MGOSERVICE CONNECTION AT 3 O' CLOCK AT MH
231.2MGOSERVICE CONNECTION AT 9 O'CLOCK AT MH
231DAGS
4.7FM
0MWL
0MGOCAPPED CONNECTION AT 9 O' CLOCK AT
0AMH02 1143
97.9TFC

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2019-04-05T03:25:33-07:00
documentation
PROPIPE
is_lateral_inspection
false