Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 5, 2019, 06:43 AM
  • 02 1134_02 1133_04052019_000128.mp4

Date
04/04/2019
W/O
761209
Weather
Dry
Operator/Surveyor
E.RUIZ
Sewer ID
Z00351
PipeID
P02916
Time
11:43 PM
Certificate
U-715-07000753
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6514
Sewer Name
02 GARFIELD AVENUE EXTENSION TRUNK
City
MONTEBELLO
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
13
Purpose
Routine Assessment
Project
RFIR_WO_761209_TV02318_APR2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
02 1134
Downstream MH
02 1133
Dir. of Survey
Downstream
Length Surveyed
340.5 ft.
Total Length
340.5 ft.
Structural Index
5
Structural Quick
5141
Structural Rating
9
O&M Index
2
O&M Quick
322M
O&M Rating
142
Overall Index
2
Overall Quick
Overall Rating
151
Pipe schematic from manhole 02 1134 to 02 1133
MH: 02 1134MH: 02 1133downstream0 ft. MWM - Water Mark, 45 %of cross sectional area0 ft. MWL - Water Level, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 11346 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start6.2 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start40.8 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 6" - 90% BLOCKED40.8 ft. RMC - Roots Medium Connection, from 03 to 11 o'clock, 30 %, within 8 inches of joint: YES43.9 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 6"68.7 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"92.2 ft. RML - Roots Medium Lateral, from 03 to 09 o'clock, 45 %, within 8 inches of joint: YES - 50% BLOCKED92.2 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"94.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"121.8 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"136.9 ft. B - Fracture, from 02 to 05 o'clock, within 8 inches of joint: YES138.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"141.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"188.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"191.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"200 ft. MGO - General Observation - SOME SURFACE SPALLING239 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"245.9 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: YES, 6" - OFFSET269.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"296.6 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"338.8 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish340 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Finish340.5 ft. MGO - General Observation - SERVICE CONNECTION AT 9 O'CLOCK AT MH340.5 ft. AMH - Downstream Manhole, Survey Ends - 02 1133

Observation photos (5)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6.2 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Medium Connection, from 03 to 11 o'clock, 30 %, within 8 inches of joint: YES

    40.8 ft. - Roots Medium Connection, from 03 to 11 o'clock, 30 %, within 8 inches of joint: YES

  • Roots Medium Lateral, from 03 to 09 o'clock, 45 %, within 8 inches of joint: YES - 50% BLOCKED

    92.2 ft. - Roots Medium Lateral, from 03 to 09 o'clock, 45 %, within 8 inches of joint: YES - 50% BLOCKED

  • Fracture, from 02 to 05 o'clock, within 8 inches of joint: YES

    136.9 ft. - Fracture, from 02 to 05 o'clock, within 8 inches of joint: YES

  • Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: YES, 6" - OFFSET

    245.9 ft. - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: YES, 6" - OFFSET

Observations (27)

DistanceCodeObservation
191.2TFC
43.9TFA
340.5MGOSERVICE CONNECTION AT 9 O'CLOCK AT MH
121.8TBA
141.1TFC
92.2RML50% BLOCKED
138.4TFC
40.8TFA90% BLOCKED
0MWM
92.2TFA
338.8FM
200MGOSOME SURFACE SPALLING
40.8RMC
6.2FM
340.5AMH02 1133
6DAGS
136.9B
68.7TBA
245.9TFDOFFSET
269.2TFC
0MWL
296.6TFA
188.5TF
340DAGS
94.6TFC
0AMH02 1134
239TFC

Properties (5)

custom_field_two
2
customer
LACSD
datetime
2019-04-04T23:43:24-07:00
documentation
PROPIPE
is_lateral_inspection
false