Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 10, 2019, 07:34 AM
  • 02 1163_02 1162_04102019_004940.mp4

Date
04/10/2019
W/O
761209
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00351
PipeID
P02947
Time
12:34 AM
Certificate
U-115-06022794
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K5924
Sewer Name
02 GARFIELD AVENUE EXTENSION TRUNK
City
MONTEBELLO
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
09
Purpose
Routine Assessment
Project
RFIR_WO_761209_TV02318_APR2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
02 1162
Downstream MH
02 1163
Dir. of Survey
Upstream
Length Surveyed
234.4 ft.
Total Length
234.4 ft.
Structural Index
4
Structural Quick
4B31
Structural Rating
71
O&M Index
2
O&M Quick
2H00
O&M Rating
94
Overall Index
3
Overall Quick
Overall Rating
165
Pipe schematic from manhole 02 1162 to 02 1163
MH: 02 1162MH: 02 1163upstream0 ft. AMH - Upstream Manhole, Survey Ends - 02 11630.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish4.9 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish49 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6"55 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"84.9 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start97.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES103.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"148.6 ft. FM - Crack Multiple, from 05 to 12 o'clock, within 8 inches of joint: YES155.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"206.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"233.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start234.4 ft. MWL - Water Level, 10 %of cross sectional area234.4 ft. MWM - Water Mark, 20 %of cross sectional area234.4 ft. AMH - Downstream Manhole, Survey Begins - 02 1162

Observation photos (3)

  • Crack Multiple, from 05 to 12 o'clock, within 8 inches of joint: YES

    85.8 ft. - Crack Multiple, from 05 to 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    137.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    149.5 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (15)

DistanceCodeObservation
79.1TFC
149.5FM
179.4TF
0.5DAGS
185.4TB
27.5TFC
0MWL
0MWM
137.3CM
234DAGS
229.5FM
0AMH02 1162
130.5TFC
234.4AMH02 1163
85.8FM

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2019-04-10T00:34:22-07:00
documentation
PROPIPE
is_lateral_inspection
false