Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 5, 2019, 07:58 AM
  • 02 1140_02 1139_04052019_011948.mp4

Date
04/05/2019
W/O
761209
Weather
Dry
Operator/Surveyor
E.RUIZ
Sewer ID
Z00351
PipeID
P02923
Time
12:58 AM
Certificate
U-715-07000753
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6514
Sewer Name
02 GARFIELD AVENUE EXTENSION TRUNK
City
MONTEBELLO
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
13
Purpose
Routine Assessment
Project
RFIR_WO_761209_TV02318_APR2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
02 1140
Downstream MH
02 1139
Dir. of Survey
Downstream
Length Surveyed
302.3 ft.
Total Length
302.3 ft.
Structural Index
5
Structural Quick
5141
Structural Rating
9
O&M Index
2
O&M Quick
2K11
O&M Rating
121
Overall Index
2
Overall Quick
Overall Rating
130
Pipe schematic from manhole 02 1140 to 02 1139
MH: 02 1140MH: 02 1139downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 11400 ft. MGO - General Observation - CAPPED CONNECTION AT 3 O' CLOCK AT MH0 ft. MWL - Water Level, 35 %of cross sectional area0 ft. MWM - Water Mark, 45 %of cross sectional area0 ft. MGO - General Observation - SERVICE CONNECTION AT 9 O'CLOCK AT MH1 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start11 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Start11 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start142.6 ft. TBA - Tap Break-In Active, at 03 o'clock, -, within 8 inches of joint: YES, 6"146.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"147.9 ft. B - Fracture, from 09 to 03 o'clock, within 8 inches of joint: YES181.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"232.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"267.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"295 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"298.9 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Finish298.9 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish302 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Finish302.3 ft. AMH - Downstream Manhole, Survey Ends - 02 1139

Observation photos (3)

  • Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Start

    11 ft. - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    11 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture, from 09 to 03 o'clock, within 8 inches of joint: YES

    147.9 ft. - Fracture, from 09 to 03 o'clock, within 8 inches of joint: YES

Observations (19)

DistanceCodeObservation
302DAGS
0AMH02 1140
295TFC
1DAGS
298.9RFJ
181.4TFC
298.9FM
232.9TFC
146.7TFC
11RFJ
147.9B
0MGOCAPPED CONNECTION AT 3 O' CLOCK AT MH
267.6TFC
142.6TBA
11FM
302.3AMH02 1139
0MWL
0MWM
0MGOSERVICE CONNECTION AT 9 O'CLOCK AT MH

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2019-04-05T00:58:55-07:00
documentation
PROPIPE
is_lateral_inspection
false